GTC60S1 Matched with GTADP-4860-C (HE49948D210B2705AW) -A Coils

Full Load Capacities based upon rated flow of 9 GPM water at 1800 CFM airflow.

COOLING FULL LOAD

Entering

Entering

Total

Sensible

Sensible

Power

Heat of

 

Fluid

Air Temp.

Capacity

Capacity

to Total

Input

Rejection

EER

Temp. (°F)

(°F)

(MBtuH)

(MBtuH)

Ratio

(KW)

(MBtuH)

 

40°

 

53.9

39.7

0.74

2.53

62.5

21.3

 

 

 

 

 

 

 

 

50°

 

53.9

40.0

0.74

2.73

63.2

19.7

 

 

 

 

 

 

 

 

60°

70° DB

53.8

40.3

0.75

2.92

63.8

18.4

 

 

 

 

 

 

 

70°

53.8

40.5

0.75

3.12

64.4

17.2

59° WB

 

 

 

 

 

 

 

80°

53.8

40.3

0.75

2.92

63.8

18.4

 

90°

 

53.9

40.0

0.74

2.73

63.2

19.7

100°

 

53.9

39.7

0.74

2.53

62.5

21.3

40°

 

58.0

41.3

0.71

2.57

66.7

22.6

 

 

 

 

 

 

 

 

50°

 

57.9

41.6

0.74

2.76

67.4

21.0

 

 

 

 

 

 

 

 

60°

75° DB

57.9

41.9

0.74

2.96

68.0

19.6

 

 

 

 

 

 

 

70°

57.8

42.2

0.73

3.16

68.6

18.3

63° WB

80°

57.9

41.9

0.72

2.96

68.0

19.6

 

90°

 

57.9

41.6

0.72

2.76

67.4

21.0

 

 

 

 

 

 

 

 

100°

 

58.0

41.3

0.71

2.57

66.7

22.6

40°

 

62.3

42.9

0.68

2.6

71.1

23.9

 

 

 

 

 

 

 

 

50°

 

62.2

43.2

0.69

2.80

71.8

22.2

 

 

 

 

 

 

 

 

60°

80° DB

62.2

43.5

0.71

3.0

72.4

20.7

70°

62.1

43.8

0.71

3.20

73.0

19.4

67° WB

 

 

 

 

 

 

 

80°

 

62.2

43.5

0.70

3.00

72.4

20.7

 

 

 

 

 

 

 

 

90°

 

62.2

43.2

0.69

2.80

71.8

22.2

 

 

 

 

 

 

 

 

100°

 

62.3

42.9

0.69

2.60

71.1

23.9

40°

 

66.7

44.4

0.67

2.64

75.7

25.3

50°

 

66.7

44.7

0.67

2.84

76.4

23.5

60°

85° DB

66.6

45.0

0.68

3.04

77.0

21.9

 

 

 

 

 

 

 

70°

66.6

45.3

0.68

3.25

77.6

20.5

71° WB

 

 

 

 

 

 

 

80°

66.6

45.0

0.68

3.04

77.0

21.9

 

 

 

 

 

 

 

 

 

90°

 

66.7

44.7

0.67

2.84

76.4

23.5

 

 

 

 

 

 

 

 

100°

 

66.7

44.4

0.67

2.64

75.7

25.3

HEATING FULL LOAD

Entering

Entering

Total

Leaving

Power

Heat of

 

Fluid

Air

Capacity

Air

Input

Absorption

COP

Temp.

Temp.

Temp. (°F)

(°F)

(MBtuH)

(°F)

(KW)

(MBtuH)

 

 

 

 

 

 

40°

 

50.6

91.0

3.72

37.9

4.0

 

 

 

 

 

 

 

45°

 

52.5

92.0

3.78

39.5

4.1

 

 

 

 

 

 

 

50°

 

54.3

92.9

3.85

41.2

4.1

 

65°

 

 

 

 

 

60°

58.1

94.9

3.98

44.5

4.3

 

 

 

 

 

 

 

70°

 

61.8

96.8

4.11

47.8

4.4

 

 

 

 

 

 

 

80°

 

65.5

98.7

4.24

51.0

4.5

 

 

 

 

 

 

 

90°

 

69.3

100.6

4.37

54.3

4.6

40°

 

49.5

95.4

3.82

36.4

3.8

 

 

 

 

 

 

 

45°

 

51.3

96.4

3.88

38.0

3.9

 

 

 

 

 

 

 

50°

 

53.1

97.3

3.95

39.6

3.9

 

 

 

 

 

 

 

60°

70°

56.8

99.2

4.09

42.8

4.1

 

 

 

 

 

 

 

70°

 

60.4

101.1

4.22

46.0

4.2

 

 

 

 

 

 

 

80°

 

64.1

102.9

4.36

49.2

4.3

 

 

 

 

 

 

 

90°

 

67.7

104.8

4.49

52.4

4.4

 

 

 

 

 

 

 

40°

 

50.0

100.7

4.28

35.4

3.4

 

 

 

 

 

 

 

45°

 

51.8

101.7

4.36

37.0

3.5

 

 

 

 

 

 

 

50°

 

53.7

102.6

4.44

38.5

3.5

 

 

 

 

 

 

 

60°

75°

57.4

104.5

4.59

41.7

3.7

 

 

 

 

 

 

 

70°

 

61.1

106.4

4.74

44.9

3.8

 

 

 

 

 

 

 

80°

 

64.8

108.3

4.89

48.1

3.9

 

 

 

 

 

 

 

90°

 

68.4

110.2

5.04

51.2

4.0

Part Load Capacities based upon rated flow of 9 GPM water at 1300 CFM airflow.

COOLING PART LOAD

Entering

Entering

Total

Sensible

Sensible

Power

Heat of

 

Fluid

Air Temp.

Capacity

Capacity

to Total

Input

Rejection

EER

Temp. (°F)

(°F)

(MBtuH)

(MBtuH)

Ratio

(KW)

(MBtuH)

 

40°

 

45.9

32.8

0.71

1.42

50.7

32.3

 

 

 

 

 

 

 

 

50°

 

44.6

32.2

0.72

1.67

50.3

26.8

60°

70° DB

43.3

31.6

0.73

1.91

49.8

22.6

 

 

 

 

 

 

 

70°

42.0

31.0

0.74

2.16

49.4

19.5

59° WB

 

 

 

 

 

 

 

80°

40.7

30.4

0.75

2.40

48.9

16.9

 

 

 

 

 

 

 

 

 

90°

 

39.4

29.8

0.76

2.65

48.4

14.9

 

 

 

 

 

 

 

 

100°

 

38.1

29.2

0.77

2.90

48.0

13.1

40°

 

49.4

34.2

0.69

1.44

54.3

34.4

50°

 

48.0

33.5

0.70

1.69

53.7

28.5

 

 

 

 

 

 

 

 

60°

75° DB

46.6

32.9

0.71

1.94

53.2

24.1

 

 

 

 

 

 

 

70°

45.2

32.3

0.71

2.19

52.6

20.7

63° WB

 

 

 

 

 

 

 

80°

43.8

31.7

0.72

2.43

52.1

18.0

 

 

 

 

 

 

 

 

 

90°

 

42.4

31.0

0.73

2.68

51.5

15.8

100°

 

41.0

30.4

0.74

2.93

51.0

14.0

40°

 

53.0

35.5

0.67

1.46

58.0

36.4

 

 

 

 

 

 

 

 

50°

 

51.5

34.8

0.68

1.71

57.3

30.1

 

 

 

 

 

 

 

 

60°

80° DB

50.0

34.2

0.68

1.96

56.7

24.3

 

 

 

 

 

 

 

70°

48.5

33.5

0.69

2.21

56.1

21.9

67° WB

 

 

 

 

 

 

 

80°

47.0

32.9

0.70

2.47

55.4

19.5

 

90°

 

45.5

32.2

0.71

2.72

54.8

17.2

 

 

 

 

 

 

 

 

100°

 

44.0

31.6

0.72

2.97

54.1

14.8

40°

 

56.8

36.7

0.65

1.48

61.8

38.5

 

 

 

 

 

 

 

 

50°

 

55.2

36.0

0.65

1.73

61.1

31.8

 

 

 

 

 

 

 

 

60°

85° DB

53.6

35.3

0.66

1.99

60.4

26.9

 

 

 

 

 

 

 

70°

52.0

34.7

0.67

2.25

59.6

23.1

71° WB

80°

50.4

34.0

0.67

2.50

58.9

20.1

 

 

 

 

 

 

 

 

 

90°

 

48.8

33.3

0.68

2.76

58.2

17.7

 

 

 

 

 

 

 

 

100°

 

47.2

32.7

0.69

3.02

57.5

15.6

HEATING PART LOAD

Entering

Entering

Total

Leaving

Power

Heat of

 

Fluid

Air

Capacity

Air

Input

Absorption

COP

Temp.

Temp.

Temp. (°F)

(°F)

(MBtuH)

(°F)

(KW)

(MBtuH)

 

 

 

 

 

 

40°

 

25.0

82.8

1.66

19.4

4.4

 

 

 

 

 

 

 

45°

 

29.4

86.0

1.93

22.9

4.5

 

 

 

 

 

 

 

50°

 

33.9

89.1

2.20

26.3

4.5

 

65°

 

 

 

 

 

60°

42.7

95.4

2.75

33.3

4.6

 

 

 

 

 

 

 

70°

 

51.6

101.7

3.29

40.3

4.6

 

 

 

 

 

 

 

80°

 

60.4

108.0

3.84

47.3

4.6

 

 

 

 

 

 

 

90°

 

69.3

114.3

4.38

54.3

4.6

 

 

 

 

 

 

 

40°

 

24.5

82.6

1.70

18.6

4.6

 

 

 

 

 

 

 

45°

 

28.8

84.8

1.98

22.0

4.7

 

 

 

 

 

 

 

50°

 

33.1

87.0

2.26

25.4

4.3

 

 

 

 

 

 

 

60°

70°

41.8

91.5

2.82

32.1

4.3

 

 

 

 

 

 

 

70°

 

50.4

95.9

3.38

38.9

4.4

 

 

 

 

 

 

 

80°

 

59.1

100.4

3.94

45.6

4.4

 

 

 

 

 

 

 

90°

 

67.7

104.8

4.50

52.3

4.4

40°

 

24.7

92.6

1.91

18.2

3.8

 

 

 

 

 

 

 

45°

 

29.1

95.7

2.22

21.5

3.8

 

 

 

 

 

 

 

50°

 

33.5

98.8

2.54

24.8

3.9

 

 

 

 

 

 

 

60°

75°

42.2

105.1

3.17

31.4

3.9

 

 

 

 

 

 

 

70°

 

51.0

111.3

3.80

38.0

3.9

 

 

 

 

 

 

 

80°

 

59.7

117.5

4.42

44.6

4.0

 

 

 

 

 

 

 

90°

 

68.4

123.7

5.05

51.2

4.0