Full Load Capacities based upon rated flow of 12 GPM of 15% methanol/mass at 1500 CFM airflow.

COOLING FULL LOAD

Entering

Entering

Total

Sensible

Sensible

Power

Heat of

 

Fluid

Air Temp.

Capacity

Capacity

to Total

Input

Rejection

EER

Temp. (°F)

(°F)

(MBtuH)

(MBtuH)

Ratio

(KW)

(MBtuH)

 

50°

 

51.4

36.1

0.70

2.42

59.7

21.3

 

 

 

 

 

 

 

 

60°

 

49.0

35.1

0.71

2.71

58.3

18.1

70°

70° DB

46.7

34.0

0.73

3.01

56.9

15.5

 

 

 

 

 

 

 

80°

44.3

33.0

0.74

3.31

55.6

13.4

59° WB

 

 

 

 

 

 

 

90°

41.9

31.9

0.76

3.61

54.2

11.6

 

 

 

 

 

 

 

 

 

100°

 

39.5

30.9

0.78

3.90

52.8

10.1

 

 

 

 

 

 

 

 

110°

 

37.1

29.8

0.80

4.20

51.5

8.8

50°

 

55.3

37.6

0.68

2.44

63.6

22.7

60°

 

52.8

36.5

0.69

2.74

62.1

19.2

 

 

 

 

 

 

 

 

70°

75° DB

50.2

35.4

0.71

3.05

60.6

16.5

 

 

 

 

 

 

 

80°

47.6

34.3

0.72

3.35

59.1

14.2

63° WB

 

 

 

 

 

 

 

90°

45.1

33.2

0.74

3.66

57.6

12.3

 

 

 

 

 

 

 

 

 

100°

 

42.5

32.2

0.76

3.97

56.0

10.7

110°

 

39.9

31.1

0.78

4.27

54.5

9.3

50°

 

59.4

39.0

0.66

2.48

67.9

23.9

 

 

 

 

 

 

 

 

60°

 

56.6

37.9

0.67

2.79

66.1

20.3

 

 

 

 

 

 

 

 

70°

80° DB

53.9

36.8

0.68

3.09

64.4

17.4

 

 

 

 

 

 

 

80°

51.1

35.6

0.70

3.39

62.7

15.1

67° WB

 

 

 

 

 

 

 

90°

48.4

34.5

0.71

3.70

61.0

13.1

 

100°

 

45.6

33.4

0.73

4.00

59.3

11.4

 

 

 

 

 

 

 

 

110°

 

42.9

32.2

0.75

4.31

57.6

10.0

50°

 

63.7

40.4

0.63

2.52

72.2

25.3

 

 

 

 

 

 

 

 

60°

 

60.7

39.2

0.65

2.83

70.4

21.5

 

 

 

 

 

 

 

 

70°

85° DB

57.8

38.0

0.66

3.13

68.5

18.4

 

 

 

 

 

 

 

80°

54.8

36.9

0.67

3.44

66.6

15.9

71° WB

90°

51.9

35.7

0.69

3.75

64.7

13.8

 

 

 

 

 

 

 

 

 

100°

 

48.9

34.5

0.71

4.06

62.8

12.0

 

 

 

 

 

 

 

 

110°

 

46.0

33.4

0.73

4.37

60.9

10.5

HEATING FULL LOAD

Entering

Entering

Total

Leaving

Power

Heat of

 

Fluid

Air

Capacity

Air

Input

Absorption

COP

Temp.

Temp.

Temp. (°F)

(MBtuH)

(KW)

(MBtuH)

 

 

(°F)

 

(°F)

 

 

 

25°

 

34.1

86.1

2.93

23.8

3.4

 

 

 

 

 

 

 

30°

 

37.2

88.0

3.04

26.5

3.6

 

 

 

 

 

 

 

40°

 

43.5

91.8

3.24

32.1

3.9

 

65°

 

 

 

 

 

50°

49.7

95.7

3.44

37.6

4.2

 

 

 

 

 

 

 

60°

 

56.0

99.5

3.64

43.2

4.5

 

 

 

 

 

 

 

70°

 

62.2

103.4

3.85

48.7

4.7

 

 

 

 

 

 

 

80°

 

68.4

107.2

4.05

54.3

5.0

25°

 

33.4

90.6

3.01

23.1

3.3

 

 

 

 

 

 

 

30°

 

36.4

92.5

3.12

25.8

3.4

 

 

 

 

 

 

 

40°

 

42.5

96.2

3.33

31.2

3.7

 

 

 

 

 

 

 

50°

70°

48.6

100.0

3.53

36.5

4.0

 

 

 

 

 

 

 

60°

 

54.7

103.8

3.74

41.9

4.3

 

 

 

 

 

 

 

70°

 

60.8

107.5

3.95

47.3

4.5

 

 

 

 

 

 

 

80°

 

66.9

111.3

4.16

52.7

4.8

25°

 

33.7

95.8

3.38

22.4

2.9

 

 

 

 

 

 

 

30°

 

36.8

97.7

3.50

25.0

3.1

 

 

 

 

 

 

 

40°

 

43.0

101.5

3.73

30.2

3.4

 

 

 

 

 

 

 

50°

75°

49.1

105.3

3.97

35.4

3.6

 

 

 

 

 

 

 

60°

 

55.3

109.1

4.20

40.7

3.8

 

 

 

 

 

 

 

70°

 

61.5

112.9

4.43

45.9

4.1

 

 

 

 

 

 

 

80°

 

67.6

116.8

4.67

51.1

4.3

 

 

 

 

 

 

 

Part Load Capacities based upon rated flow of 12 GPM of 15% methanol/mass at 1150 CFM airflow.

COOLING PART LOAD

Entering

Entering

Total

Sensible

Sensible

Power

Heat of

 

Fluid

Air Temp.

Capacity

Capacity

to Total

Input

Rejection

EER

Temp. (°F)

(°F)

(MBtuH)

(MBtuH)

Ratio

(KW)

(MBtuH)

 

50°

 

39.1

28.3

0.72

1.35

43.7

29.0

 

 

 

 

 

 

 

 

60°

 

37.1

27.5

0.74

1.60

42.6

23.2

 

 

 

 

 

 

 

 

70°

70° DB

35.1

26.6

0.76

1.86

41.4

18.9

 

 

 

 

 

 

 

80°

33.1

25.8

0.78

2.11

40.3

15.7

59° WB

90°

31.1

25.0

0.80

2.37

39.2

13.1

 

 

 

 

 

 

 

 

 

100°

 

29.1

24.2

0.83

2.62

38.0

11.1

 

 

 

 

 

 

 

 

110°

 

27.1

23.3

0.86

2.88

36.9

9.4

50°

 

42.1

29.5

0.70

1.36

46.7

31.0

 

 

 

 

 

 

 

 

60°

 

39.9

28.6

0.72

1.62

45.4

24.7

 

 

 

 

 

 

 

 

70°

75° DB

37.7

27.7

0.73

1.88

44.2

20.1

80°

35.6

26.9

0.76

2.14

42.9

16.6

63° WB

 

 

 

 

 

 

 

90°

 

33.4

26.0

0.78

2.41

41.7

13.9

 

 

 

 

 

 

 

 

100°

 

31.3

25.2

0.80

2.67

40.4

11.7

 

 

 

 

 

 

 

 

110°

 

29.1

24.3

0.83

2.93

39.1

9.9

50°

 

45.2

30.6

0.67

1.38

49.9

27.1

60°

 

42.8

29.7

0.69

1.64

48.5

24.2

70°

80° DB

40.5

28.8

0.71

1.91

47.0

21.3

 

 

 

 

 

 

 

80°

38.2

27.9

0.73

2.17

45.6

18.3

67° WB

 

 

 

 

 

 

 

90°

35.9

27.0

0.75

2.43

44.2

15.4

 

 

 

 

 

 

 

 

 

100°

 

33.6

26.1

0.78

2.69

42.8

12.5

 

 

 

 

 

 

 

 

110°

 

31.3

25.2

0.80

2.95

41.4

9.6

50°

 

48.4

31.7

0.65

1.40

53.2

34.5

 

 

 

 

 

 

 

 

60°

 

45.9

30.7

0.67

1.67

51.6

27.5

 

 

 

 

 

 

 

 

70°

85° DB

43.4

29.8

0.69

1.93

50.0

22.5

 

 

 

 

 

 

 

80°

41.0

28.9

0.70

2.20

48.5

18.6

71° WB

 

 

 

 

 

 

 

90°

38.5

27.9

0.73

2.47

46.9

15.6

 

 

 

 

 

 

 

 

 

100°

 

36.0

27.0

0.75

2.73

45.3

13.2

110°

 

33.5

26.1

0.78

3.00

43.8

11.2

HEATING PART LOAD

Entering

Entering

Total

Leaving

Power

Heat of

 

Fluid

Air

Capacity

Air

Input

Absorption

COP

Temp.

Temp.

Temp. (°F)

(°F)

(MBtuH)

(°F)

(KW)

(MBtuH)

 

 

 

 

 

 

25°

 

23.8

85.5

2.17

16.1

3.2

 

 

 

 

 

 

 

30°

 

26.3

87.7

2.21

18.5

3.5

 

 

 

 

 

 

 

40°

 

31.3

92.0

2.28

23.3

4.0

 

65°

 

 

 

 

 

50°

36.3

96.3

2.35

28.1

4.5

 

 

 

 

 

 

 

60°

 

41.4

100.6

2.43

32.9

5.0

 

 

 

 

 

 

 

70°

 

46.4

104.9

2.50

37.7

5.4

 

 

 

 

 

 

 

80°

 

51.4

109.2

2.57

42.4

5.9

25°

 

23.3

90.0

2.23

15.7

3.1

 

 

 

 

 

 

 

30°

 

25.7

92.2

2.27

18.0

3.3

 

 

 

 

 

 

 

40°

 

30.6

96.4

2.34

22.6

3.8

 

 

 

 

 

 

 

50°

70°

35.5

100.6

2.42

27.3

4.3

 

 

 

 

 

 

 

60°

 

40.4

104.8

2.49

31.9

4.7

 

 

 

 

 

 

 

70°

 

45.3

109.0

2.57

36.6

5.2

 

 

 

 

 

 

 

80°

 

50.2

113.3

2.64

41.2

5.6

 

 

 

 

 

 

 

25°

 

23.5

95.3

2.51

15.2

2.8

 

 

 

 

 

 

 

30°

 

26.0

97.4

2.55

17.4

3.0

 

 

 

 

 

 

 

40°

 

31.0

101.7

2.63

22.0

3.4

 

 

 

 

 

 

 

50°

75°

35.9

105.9

2.71

26.5

3.9

 

 

 

 

 

 

 

60°

 

40.9

110.2

2.80

31.0

4.3

 

 

 

 

 

 

 

70°

 

45.8

114.5

2.88

35.5

4.7

 

 

 

 

 

 

 

80°

 

50.8

118.7

2.97

40.0

5.0

Form No.