10PP38+ Pellet Stove3-90-08422R27_09/12
#2 Preferred method
This method also provides excellent venting for
normal operation but requires the stove to be installed
farther from the wall. The vertical portion of the vent
shouldbe threeto vefeet highand at leastthree
inches from a combustible wall. This vertical section
will provide natural draft in the event of a power failure.
If the stove is installed below grade be sure the
vent termination is at least 18" above grade. The outlet
must also be 1 foot from the house/building.
Note: Do not place joints within wall pass-
throughs.
#1 Preferred method
This method provides excellent venting for normal
operation and allows the stove to be installed closest
to the wall. Two inches from the wall is safe; however,
four inches allows better access to remove the rear
panel. The vertical portion of the vent should be three
tovefeethigh.Thisverticalsectionwill helpprovide
natural draft in the event of a power failure. note: do
not place joints within wall pass-throughs.
venting
36" min
clearance to any
combustible
material
12" min. wall to outlet
caution
Keep combustible materials (such as grass, leaves,
etc.) at least 3 feet away from the ue outlet on the
outside of the building.
Fig. 8
3 ft.
to
combustibles
3 ft.
to combustibles
Fig. 9
3 ft.
to
combustibles
3 ft.
to combustibles