5
P61A!Pellet!Stove
Installing
Place!the!stove!on!a!noncombustible!floor!protector
that!extends!6!inches!to!the!front,!6!inches!to!the!sides
and!1!inch!to!the!rear!of!the!stove.!The!minimum!floor
protector!material!is!24!gauge!sheet!metal.
Place!the!stove!away!from!combustible!walls!at!least
as!far!as!shown!in!figures!3,4!and!5.!Please!note!the
difference!in!side!wall!clearance!with!and!without!side
shields.
Note!that!the!clearances!shown!are!minimum!for
safety!but!do!not!leave!much!room!for!access!when!clean-
ing!or!servicing.!Please!take!this!into!account!when!plac-
ing!the!stove.
Connect!the!power!cord!to!a!120!V.A.C.!60Hz
grounded!receptacle.!(A!surge!protector!is!recommened
to!protect!the!circuit!board).
Prior!to!installing!the!flue!pipe,!connect!a!draft!meter
to!the!stove!as!shown!in!fig.!6.!!(The!draft!meter!must
have!a!minimum!range!of!0-.5).!However,!prior!to!taking
the!draft!reading!be!sure!all!doors!and!windows!in!the
home!are!closed.!!Record!the!draft!reading_______.!!If
this!reading!is!more!than!.05"!lower!than!the!unconnected
reading,!check!for!possible!restrictions!or!the!need!for
outside!air!(see!page!7).

Mobile!Home!Installation

Fig.!5
18"

Without!Side!Shields

FLOOR!PROTECTOR
Fig.!6
Installation
When!installing!this!unit!in!a!mobile!home!several!re-
quirements!must!be!followed:
1.!The!unit!must!be!bolted!to!the!floor.!This!can!be
done!with!1/4"!lag!screws!through!the!2!holes!in!the!base
plate.
2.!The!unit!must!also!be!connected!for!the!outside!air.
See!page!8.
3.!Floor!protection!and!clearances!must!be!followed
as!shown.
4.!Unit!must!be!grounded!to!the!metal!frame!of!the
mobile!home.
CAUTION:!This!appliance!must!be!vented!to!the!out-
side.
Due!to!high!temperatures,!the!stove!should!be!placed
out!of!traffic!and!away!from!furniture!and!draperies.
Children!and!adults!should!be!alerted!to!the!hazards!of
high!surface!temperatures!and!should!stay!away!!to!avoid
burn!to!skin!and/or!clothing.
Young!children!should!be!carefully!supervised!when
they!are!in!!the!same!room!as!the!stove.
Clothing!and!other!flammable!materials!should!not!be
placed!on!or!near!this!unit.
Installation!and!repair!of!this!Harman!Stove!should!be
done!by!a!qualified!service!person.!The!appliance!should!be
inspected!before!use!and!at!least!annually!by!a!qualified
service!person.!More!frequent!cleaning!will!be!required.!It
is!imperative!that!control!compartments,!burners,!and!circu-
lating!air!passageways!of!the!stove!be!kept!clean.
FLOOR!PROTECTOR
9"!With!Side!Shields
13"!Without!Side!Shields
9"-13"
Fig.!3
9"-13"
Fig.!4
2"
6"

With!Side!Shields

FLOOR!PROTECTOR
12"
6"
6"
1"