Heatilator • Novus NDV Series • 4055-187 Rev. V • 1/1260
Troubleshooting (continued)
Symptom Possible Cause Corrective Action
3. (Continued) C.Failed valve. Turn the valve knob to the ON position. Place the ON/OFF switc h
in the ON position. Check the millivolt meter a the thermopile
terminals. The millivolt meter should read greater than 125mV. If the
reading is acceptable, and if the burner does not come on, replace
the gas valve.
D.Plugged burne r ori ce. Check the burner ori ce for stoppage. Remove stoppage.
E.Wall switch o r wires. Check the wall switch and wires for proper connections. Place t he
jumper wires across the terminals at the wall switch. If the burner
comes on, replace the wall switch. If the wall switch is OK, plac e
the jumper wires across the wall switch wires at the gas valve. If the
burner comes on, the wires are faulty or connections a re bad.
4. Frequent pilot outage
problem. A.Pil ot ame may be too high or
too low, or blowing out (high
pressure), causing pilot safety
to drop out.
Clean thermocouple and adjust the pilot ame for proper ame
impingement. Follow lighting instructions carefully.
5. The pilot and main
burner extinguish while in
operation.
A.N o LP in tank. Check the LP (propane) tank. Re ll the fuel tank.
B.Impro per gas inlet pressure. Verify with manometer. NG should read 5-14 inches w.c. LP
should read 10-14 inches w.c.
C.Inner vent pipe leak ing exhaust
gases back into the system. Check venting system for damage. Replac e/repair improperly
assembled pipe sections.
D.Glass installed im properly. Check to ensure glass is installed properly. Replace glass panel
assembly.
E.Failed thermopile or
thermocouple. Replace pilot if necessary.
F.Improper vent c ap installation. Chec k for proper installation and freedom from debris or blockage.
6. Glass soots. A.Flame im pingement. Adjust the log set so that the ame does not excessively impinge on
it. Refer to log instructions.
B.Impro per air shutter setting. Refer to manual for shut ter set points. Ensure that set point is
correct for appliance/gas type. If unit has adjustable shutter, it may
be necessary to increase shutter opening.
C.Debri s around air shutter. Inspect the opening at the base of the burner. NO MATERIAL
SHOULD BE PLACED IN THIS OPENING.
7.Flame bur ns blue and lifts
off burner. A. Insuf cient oxygen being
supplied. Ensure that the vent cap is installed properly and free of debris.
Ensure that the vent system joints are tight and have no leaks.
Ensure that no debris has been placed at the base of, or in the area
of the air holes in the center of the base pan beneath the burner.
Ensure that the glass is tightened properly on the unit, particular ly
on top corners.