Hearth and Home Technologies RSW-41, RSW-47 manual Installing an ST375 Square Termination Cap

Models: RSW-41 RSW-47

1 32
Download 32 pages 33.05 Kb
Page 24
Image 24

RSW-41 AND RSW-47 SERIES INSTALLATION INSTRUCTIONS

c.For installations utilizing an ST375 square termination cap the last chimney section must not be more than 4-1/2 in. below the chase top. See Figure 24.

d.For installation utilizing a TS345/TS345P Square Termination Cap, the uppermost chimney section must not be more than 3 in. below the chase top. See Figure 25.

e.Attach the chase top (CT35) to the top of the chase.

f.Install the termination cap, following the instructions provided with it.

Figure 24 - Installing an ST375 Square

Termination Cap

Figure 25 - Installing a TS345/TS345P

Square Termination Cap

WARNING!

Never install a single wall slip section or smoke-pipe in a chase structure. The higher temperature of this single wall pipe may radiate sufficient heat to combustible chase materials to cause a fire.

WARNING!

Detailed instructions for installation of the chase top, storm collar and termination cap are packaged with these parts. To avoid danger of fire, all instructions must be strictly followed, including the provision of air space clearance between chimney system and enclosure. To protect against the effects of corrosion on those parts exposed to the weather, we recommend that the chase top and termination cap be painted with a rust- resistant paint.

24

26023 Rev L

08/04

Page 24
Image 24
Hearth and Home Technologies RSW-41, RSW-47 manual Installing an ST375 Square Termination Cap