Heat & Glo LifeStyle COSMO-I35, COSMO-I30 owner manual Mantel and Wall Projections, Side View

Models: COSMO-I35 COSMO-I30

1 40
Download 40 pages 33.78 Kb
Page 18
Image 18

SIDE VIEW

TOP VIEW

1-1/2 IN.

BD

CD

SURROUND

APPLIANCE

AD

SURROUND

APPLIANCE

MINIMUM FIREPLACE SIZE

 

Location

COSMO-I35

COSMO-I30

 

 

 

 

 

 

Inches

Millimeters

Inches

Millimeters

 

 

 

 

 

 

 

 

AD

Alternate Unit Width

33-3/16

843

29-1/16

738

 

 

 

 

 

 

BD

Alternate Unit Depth

15-1/16

383

13-7/8

352

 

 

 

 

 

 

CD

Alternate Unit Height

22-9/16

573

19-1/16

484

 

 

 

 

 

 

*Note: If exhaust collar on insert and fireplace damper do not line up, add 4 inches (102 mm) to minimum fireplace height for bends in vent pipe.

Figure 5.2 Fireplace Opening - Deep Surround

B. Mantel and Wall Projections

WARNING! Risk of Fire! Comply with all minimum clear- ances to combustibles as specified. Framing or finishing material closer than the minimums listed must be construct- ed entirely of noncombustible materials (i.e., steel studs, concrete board, etc).

Clearance to combustible material under the insert is 1/4 inch (6 mm). Clearance from top of fireplace opening for combustibles extending 12 inches max. is 12 inches.

Use leveling legs to raise insert minimum 1/4 inch (6 mm) above combustible material or outer wrap of factory built firebox.

Combustible facings must not extend behind the insert surround. For non-combustible material specifications refer to section 1.E.

EXISTING NON-COMBUSTIBLE FACING

12 IN. MAX.

12 IN. MIN.

Figure 5.3 Mantel Clearances

18

Heat & Glo • Cosmo-I30, Cosmo-I352239-900 Rev. H • 1/11

Page 18
Image 18
Heat & Glo LifeStyle COSMO-I35, COSMO-I30 owner manual Mantel and Wall Projections, Side View