NOTES

Replacement of the refrigeration cycle.

1.When replacing the refrigeration cycle, be sure to discharge the refrigerant system using a FreonTM recovery System.

If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the FreonTM. Leave the valve in place after servicing the system.

2.After discharging the unit completely, remove the desired component, and unbrace the pinch-off tubes.

3.Solder service valves into the pinch-off tube ports, leaving the valves open.

4.Solder the pinch-off tubes with Service valves.

5.Evacuate as follows.

1)Connect the vacuum pump, as illustrated Fig. 17A.

2)Start the vacuum pump, slowly open manifold valves A and B with two full turns counterclockwise and leave the valves closed. The vacuum pump is now pulling through valves A and B up to valve C by means of the manifold and entire system.

CAUTION

If high vacuum equipment is used, just crack valves A and B for a few minutes, then open slowly with the two full turns counterclockwise. This will keep oil from foaming and being drawn into the vacuum pump.

3)Operate the vacuum pump for 20 to 30 minutes, until 600 microns of vacuum is obtained. Close valves A and B, and observe vacuum gauge for a few minutes. A rise in pressure would indicate a possible leak or moisture remaining in the system. With valves A and B closed, stop the vacuum pump.

4)Remove the hose from the vacuum pump and place it on the charging cylinder. See Fig. 17B. Open valve C.

Discharge the line at the manifold connection.

5)The system is now ready for final charging.

6.Recharge as follows :

1)Refrigeration cycle systems are charged from the High-side. If the total charge cannot be put in the High-side, the balance will be put in the suction line through the access valve which you installed as the system was opened.

2)Connect the charging cylinder as shown in Fig. 17B. With valve C open, discharge the hose at the manifold connection.

3)Open valve A and allow the proper charge to enter the system. Valve B is still closed.

4)If more charge is required, the high-side will not take it. Close valve A.

5)With the unit running, open valve B and add the balance of the charge.

a.Do not add the liquid refrigerant to the Low- side.

b.Watch the Low-side gauge; allow pressure to rise to 30 lbs.

c.Turn off valve B and allow pressure to drop.

d.Repeat steps B and C until the balance of the charge is in the system.

6)When satisfied the unit is operating correctly, use the pinch-off tool with the unit still running and clamp on to the pinch-off tube. Using a tube cutter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos solder and solder pinch-off tube closed. Turn off the unit, allow it to set for a while, and then test the leakage of the pinch-off connection.

10

Page 10
Image 10
Heat Controller BG-123A, BG-81A, BG-101A service manual

BG-101A, BG-123A, BG-81A specifications

The Heat Controller series, comprising BG-81A, BG-101A, and BG-123A, represents a new benchmark in energy-efficient temperature management solutions. Engineered for both residential and commercial applications, these models offer versatility, reliability, and innovative technology designed to enhance user comfort while minimizing energy consumption.

The BG-81A model is compact yet powerful, making it an ideal choice for smaller spaces or individual rooms. Its key features include a programmable thermostat, allowing users to set specific heating schedules tailored to their needs. The BG-81A employs advanced inverter technology, which ensures that the unit maintains desired temperatures with minimal temperature fluctuations. This feature not only improves comfort levels but also significantly reduces energy costs by optimizing power usage.

Moving up in capacity, the BG-101A boasts enhanced heating capabilities suitable for medium-sized areas. It is equipped with a dual heating mode, allowing users to switch between energy-saving and high-efficiency settings. This flexibility makes the BG-101A adaptable to various environmental conditions, providing reliable warmth during the coldest months. Additionally, it features a built-in air purification system that ensures the delivery of high-quality air by trapping dust, allergens, and other particulates, benefiting users with respiratory sensitivities.

At the top of the lineup, the BG-123A is designed for larger spaces, combining robust performance with cutting-edge technology. It incorporates smart connectivity features, allowing users to control the heating system remotely via a mobile app. This functionality not only enhances convenience but also aids in energy management, as users can monitor and adjust settings in real time. The BG-123A also has an advanced temperature sensor that adapts the heating output based on the specific needs of the environment, ensuring optimal comfort while conserving energy.

All three models feature quiet operation, ensuring they can effectively function in bedrooms or offices without disrupting daily activities. Additionally, they are designed with user-friendly interfaces and minimal maintenance requirements, making them accessible for a wide range of users.

Overall, the Heat Controller BG series exemplifies modern heating solutions, combining efficiency, smart technology, and user-centric design for an unparalleled heating experience.