Heat Controller HCG**V1E, HMG**X1E Control Board Operation, Air Handler Model, Models Number

Models: HMG**X1E HCG**V1E HMG**F1E

1 32
Download 32 pages 47.39 Kb
Page 29
Image 29

HMG**X1E & HCG**V1E

 

 

 

 

 

240 VAC, 50 & 60 Hz, Single Phase

 

 

208 VAC, 50 & 60 Hz, Single Phase

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat KiT

 

MCA

 

 

 

MOP

 

 

MCA

 

 

MOP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Handler

Model

 

Circuit A

Circuit B

 

Circuit C

Single Circuit

Circuit A

 

Circuit B

Circuit C

 

Single Circuit

Circuit A

Circuit B

 

Circuit C

Single Circuit

Circuit A

Circuit B

Circuit C

 

Single Circuit

 

Models

Number

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H6HK-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HMG24X1E

None

 

4.5

-

 

-

4.5

15

 

-

-

 

15

4.8

-

 

-

4.8

15

-

-

 

15

 

005H-XX

 

29.5

-

 

-

29.5

30

 

-

-

 

30

26.4

-

 

-

26.4

30

-

-

 

30

 

HMG30X1E

008H-XX

 

44.1

-

 

-

44.1

45

 

-

-

 

45

39.1

-

 

-

39.1

40

-

-

 

40

 

&

010H-XX

 

54.5

-

 

-

54.5

60

 

-

-

 

60

48.1

-

 

-

48.1

50

-

-

 

50

 

HCG24V1E

015H-XX

 

54.5

25.0

 

-

68.1

60

 

30

-

 

80

48.1

21.7

 

-

69.8

50

25

-

 

70

 

HCG30V1E

009Q-XX

 

-

-

 

-

31.6

-

 

-

-

 

35

-

-

 

-

28.2

-

-

-

 

30

 

015Q-XX

 

-

-

 

-

47.8

-

 

-

-

 

50

-

-

 

-

42.3

-

-

-

 

45

 

 

 

 

 

 

 

 

 

 

None

 

4.5

-

 

-

4.5

15

 

-

-

 

15

4.8

-

 

-

4.8

15

-

-

 

15

 

HMG36X1E

005H-XX

 

29.5

-

 

-

29.5

30

 

-

-

 

30

26.4

-

 

-

26.4

30

-

-

 

30

 

008H-XX

44.1

-

 

-

44.1

45

 

-

-

 

45

39.1

-

 

-

39.1

40

-

-

 

40

 

HMG42X1E

 

 

 

 

 

 

010H-XX

 

54.5

-

 

-

54.5

60

 

-

-

 

60

48.1

-

 

-

48.1

50

-

-

 

50

 

&

 

 

 

 

 

 

 

015H-XX

 

54.5

25.0

 

-

68.1

60

 

30

-

 

80

48.1

21.7

 

-

69.8

50

25

-

 

70

 

HCG36V1E

 

 

 

 

 

 

 

020H-XX

 

54.5

50.0

 

-

104.5

60

 

60

-

 

110

48.1

43.3

 

-

91.4

50

45

-

 

100

 

HCG42V1E

 

 

 

 

 

 

 

009Q-XX

 

-

-

 

-

31.6

-

 

-

-

 

35

-

-

 

-

28.2

-

-

-

 

30

 

 

015Q-XX

 

-

-

 

-

47.8

-

 

-

-

 

50

-

-

 

-

42.3

-

-

-

 

45

 

 

None

 

6.3

-

 

-

6.3

15

 

-

-

 

15

6.8

-

 

-

6.8

15

-

-

 

15

 

 

005H-XX

31.3

-

 

-

31.3

35

 

-

-

 

35

28.4

-

 

-

28.4

30

-

-

 

30

 

HMG48X1E

008H-XX

 

45.8

-

 

-

45.8

50

 

-

-

 

50

41.1

-

 

-

41.1

45

-

-

 

45

 

010H-XX

56.3

-

 

-

56.3

60

 

-

-

 

60

50.1

-

 

-

50.1

60

-

-

 

60

 

HMG60X1E

 

 

 

 

 

 

015H-XX

 

56.3

25.0

 

-

81.3

60

 

30

-

 

90

50.1

21.7

 

-

71.8

60

25

-

 

80

 

&

 

 

 

 

 

 

 

020H-XX

 

56.3

50.0

 

-

106.3

60

 

60

-

 

110

50.1

43.3

 

-

93.4

60

45

-

 

100

 

HCG48V1E

 

 

 

 

 

 

 

024H-XX

 

56.3

50.0

 

25.0

131.3

60

 

60

60

 

150

50.1

43.3

 

21.7

115.1

60

45

45

 

125

 

HCG60V1E

 

 

 

 

 

 

 

029H-XX

 

56.3

50.0

 

50.0

156.3

60

 

60

60

 

175

50.1

43.3

 

43.3

136.8

60

45

45

 

150

 

 

009Q-XX

 

-

-

 

-

33.3

-

 

-

-

 

35

-

-

 

-

30.2

-

-

-

 

35

 

 

015Q-XX

 

-

-

 

-

49.6

-

 

-

-

 

50

-

-

 

-

44.3

-

-

-

 

45

 

Table 11. HMG**X1E & HCG**V1E Minimum Circuit Ampacity & Maximum Overcurrent Protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control Signal & MODE

 

Operation

 

 

Total KW

 

 

 

 

 

 

 

Board Action

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5 KW

 

 

Stage 1 Heat on instantly

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat blower on after 3 second delay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10 KW

 

 

Stage 1 Heat on instantly

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat blower on after 3 second delay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stage 1 Heat on instantly

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15 KW

 

 

Heat blower on after 3 second delay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stage 2 Heat on after 5 second delay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stage 1 Heat on instantly

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20 KW

 

 

Heat blower on after 3 second delay

 

 

 

 

 

 

 

 

 

 

On

 

 

 

 

 

Stage 2 Heat on after 5 second delay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W1 only

 

 

 

 

 

 

 

 

 

 

 

Stage 3 Heat on after 10 second delay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EHEAT

 

 

 

 

 

 

 

 

 

 

 

 

Stage 1 Heat on instantly

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25 KW

 

 

Heat blower on after 3 second delay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stage 2 Heat on after 5 second delay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stage 3 Heat on after 10 second delay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stage 1Heat on instantly

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat blower on after 3 second delay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30 KW

 

 

Stage 2 Heat on after 5 second delay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stage 3 Heat on after 10 second delay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stage 4 Heat on after 15 second delay

 

 

 

 

 

 

 

 

 

 

Off

 

 

 

 

 

 

 

Heat stages off instantly

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Blower off after 15 second delay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 12. Control Board Operation

29

Page 29
Image 29
Heat Controller HCG**V1E, HMG**X1E, HMG**F1E Control Board Operation, Air Handler Model, Models Number