HT Series Ratings

Engineering Design Guide

HTV/HTD/HTH SERIES

Heat Controller, Inc.

 

 

 

Heat ControllerTwoGeoMaxStage Geothermal2 n GeothermalHeat PumpHeatSystemsPump Systems

HT Series Ratings

ARI/ASHRAE/ISO 13256-1

at EWT (Entering Water Temperature)

HTV/HTD/HTH024

HTV/HTD/HTH036

HTV/HTD/HTH048

HTV/HTD/HTH060

HTV/HTD/HTH070

Heating capacities based upon 68°F DB, 59°F WB entering air temperature.

HT Electrical Data

 

Voltage

 

Min/Max

 

Compressor

 

Fan Motor

Total Unit

 

 

Model

Code

Voltage

Voltage

QTY

 

RLA

 

LRA

FLA

FLA

MCA

Max/Fuse

024

1

208/230-60/1

197/254

1

 

10.3

 

52.0

3.9

18.6

21.2

30

 

 

 

 

 

 

 

 

 

 

 

 

 

036

1

208/230-60/1

197/254

1

 

16.7

 

82.0

3.9

25.0

29.2

45

 

 

 

 

 

 

 

 

 

 

 

 

 

048

1

208/230-60/1

197/254

1

 

21.2

 

96.0

6.9

32.5

37.8

50

 

 

 

 

 

 

 

 

 

 

 

 

 

060

1

208/230-60/1

197/254

1

 

25.6

 

118.0

6.9

36.9

43.3

60

 

 

 

 

 

 

 

 

 

 

 

 

 

070

1

208/230-60/1

197/254

1

 

27.2

 

150.0

6.9

38.5

45.3

70

 

 

 

 

 

 

 

 

 

 

 

 

 

Min/Max Voltage of 197/254

HACR circuit breaker in USA only

All fuses Class RK-5

Wire size based on 60°C copper conductor and Minimum Circuit Ampacity.

Wire length based on one way measurement with 2% voltage drop