R410a Application and Service Guide
Figure 1. PPM of Water Absorbed Over Time
POE: Continues to absorb moisture
PPM of
Water
Mineral Oils: Max water absorption, excess separates
24 hrs
Time
•A vacuum pump will not adequately remove mois- ture from the POE lubricants. Use a filter drier and replace whenever the system is opened.
•POEʼs can be irritating to the skin
•POEʼs can damage some roofing membrane materi- als
•POEʼs are better solvents than mineral oils
•Leave POE Refrigerant circuits open no more than 15 minutes
Approved POE Oils for Copeland R410a and R407c
compressors are:
•Copeland Ultra 22CC
•Copeland 3MA (scroll compressors only)
•Mobil EAL Arctic 22CC
•ICI (Virginia KMP) Emkarate RL32CF
•Thermal Zone 22CC
Service Tools
It is recommended that a separate R410a tool set be em- ployed to avoid the problem of mixing refrigerants on the job site.
Gauge Manifold Sets
A specific gauge set for use with R410a is required. These will allow pressure measurements to 800 psig on the high side and 250 psig on the low side. Hoses should have a service rating of 800 psig.
Vacuum Pump
A 500 micron evacuation IS NOT ADEQUATE to sepa- rate moisture from POE oil in R410a systems. It is for this reason that an R410a approved liquid line filter drier should be installed everytime the system is opened.
Leak Detectors
An approved leak detector for HFC refrigerants can be
used in R410a systems. Older R22 leak detectors and Ha- lide torch leak detectors can not be used in R410a service. NEVER use a mixture of air and R410a to leak check.
The mixture may become flammable at pressures above amtospheric. Nitrogen and trace R410a or nitrogen alone can be safely used for leak testing in R410a systems. Six approved leak detector types for alternative refrigerants are:
•
•Halogen specific
•Compound specific
•Infrared based
•Flourescent dyes
•Ultrasonic
Active Recovery Equipment (Self-Contained)
Due to the increased pressure of R410a, recovery equip- ment has been redesigned to handle these higher pres- sures. Recovery equipment rated for R410a must be used. Recovery cylinders must have a service pressure rating of 400 psig (DOT 4BA 400 and DOT 4BW 400 are accept- able). DO NOT USE STANDARD DOT RECOVERY
OR STORAGE CYLINDERS WITH A 300 PSIG RAT- ING WITH R410A!
Other Service Tools
Other service tools such as the micron gauge and vacuum pump are adequate for both R22 and R410a service.
Service Procedures
Leak Detection
If an R410a system develops a leak, the technician does not have to recover the the remaining refrigerant from the system before
The Refrigerant Recycling Regulations Section 608 of the Clean Air Act states that the technician must find and
repair substantial leaks of systems with 50 lbs. or more of
refrigerant. Substantial leaks are defined as:
Page 4