13
Dimensional Data

Connections (In.) Approx.

Model Dimensions (In.) Coil Ship Wt.

No. A B C D W Inlet Suction Drain (Lbs.)

13 12 5/8 12 3/8 11 7/16 1 3/8 14 1/4 3/8 OD 3/8 ID 1/2 OD 16

17 15 5/8 12 3/8 14 7/16 1 3/8 17 1/4 3/8 OD 1/2 ID 1/2 OD 17

23 21 5/8 12 3/8 21 1/16 7/8 22 3/4 3/8 OD 1/2 ID 1/2 OD 22

30 26 1/8 12 3/8 25 13/16 1 27 3/4 3/8 OD 1/2 ID 1/2 OD 27

43 36 5/16 - - - 38 1/2 OD 1/2 ID 1/2 OD 40

High Profile Unit Cooler
Dimensional Diagram
Mounting

Using dimensions given in Dimensional Diagram and Data,

install mounting screws for rear hangers and slide hanger

slots onto screws before tightening. Open cabinet and install

screws through top, front mounting holes to ceiling of box.

Expansion Valve Recommendations

25°F Sat. Suction Temp. 20°F Sat. Suction Temp.
Model BTUH @ R-22 BTUH @ R-22
Size 10°F TD Alco Sporlan 15°F TD Alco Sporlan
13 1300 1950 EFV-1/5C
17 1700 HFS-1/4HC EFV-1/5C 2550 HFS-1/4HC
23 2300 3450 EFV-1/3C
30 3000 4500 HFS-1/2HC
43* 4300 HFES-1/2HC EFVE-1/2C 6450 HFES-1HC EFVE-1C
* Size 43 uses external equalized valve.

Replacement Parts

Description All Sizes Part Number
115V Motor 25303201
208/230V Motor 25303301
Fan Blade 23100201
Fan Guard H50328
Motor Mount 23101401
FOR FOOD
SERVICE
INSTALLATIONS
. . . seal any joint
between unit cooler
and cooler liner
with a sealant
listed by the
National Sanitation
Foundation,
Standard 51
High Profile Vintage Unit CoolerK = Coated Coil A = 115-1-60 (Optional) B = 208/230-1-60 Size
NOMENCLATURE

C (K) 43 B G