Performance Data
Model BMA Air Defrost 60 Hz
Model
Capacity |
|
| Fan Data |
|
|
| Air Throw*† |
|
| |||
10°F TD |
| 6°C TD |
|
|
| Diameter | Extended |
| Diffused | |||
25°F SST | - 4°C SST | No. | CFM | m3h | (Standard) | (Optional) | ||||||
|
| |||||||||||
BTUH |
| Watts |
|
|
| in. | mm | ft. | m | ft. | m |
BMA130 | 13,000 | 3,810 | 1 | 2,300 | 3,910 | 18 | 457 | 65 | 20 | 50 | 15 |
|
|
|
|
|
|
|
|
|
|
|
|
BMA155 | 15,500 | 4,540 | 1 | 2,200 | 3,740 | 18 | 457 | 65 | 20 | 50 | 15 |
|
|
|
|
|
|
|
|
|
|
|
|
BMA245 | 24,500 | 7,180 | 2 | 4,600 | 7,820 | 18 | 457 | 65 | 20 | 50 | 15 |
|
|
|
|
|
|
|
|
|
|
|
|
BMA300 | 30,000 | 8,790 | 2 | 4,400 | 7,480 | 18 | 457 | 65 | 20 | 50 | 15 |
|
|
|
|
|
|
|
|
|
|
|
|
BMA365 | 36,500 | 10,690 | 3 | 6,900 | 11,730 | 18 | 457 | 65 | 20 | 50 | 15 |
|
|
|
|
|
|
|
|
|
|
|
|
BMA450 | 45,000 | 13,180 | 3 | 6,600 | 11,220 | 18 | 457 | 65 | 20 | 50 | 15 |
|
|
|
|
|
|
|
|
|
|
|
|
BMA510 | 51,000 | 14,940 | 4 | 9,200 | 15,640 | 18 | 457 | 65 | 20 | 50 | 15 |
|
|
|
|
|
|
|
|
|
|
|
|
BMA600 | 60,000 | 17,570 | 4 | 8,800 | 14,960 | 18 | 457 | 65 | 20 | 50 | 15 |
|
|
|
|
|
|
|
|
|
|
|
|
BMA710 | 71,000 | 20,790 | 5 | 10,500 | 17,850 | 18 | 457 | 65 | 20 | 50 | 15 |
Model BMA Air Defrost 50 Hz‡
Model
Capacity |
|
| Fan Data |
|
|
| Air Throw*† |
|
| |||
10°F TD |
| 6°C TD |
|
|
| Diameter | Extended |
| Diffused | |||
25°F SST | - 4°C SST | No. | CFM | m3h | (Standard) | (Optional) | ||||||
|
| |||||||||||
BTUH |
| Watts |
|
|
| in. | mm | ft. | m | ft. | m |
BMA130 | 11,960 | 3,500 | 1 | 2,070 | 3,520 | 18 | 457 | 60 | 18.5 | 45 | 13.5 |
|
|
|
|
|
|
|
|
|
|
|
|
BMA155 | 14,260 | 4,180 | 1 | 1,980 | 3,370 | 18 | 457 | 60 | 18.5 | 45 | 13.5 |
|
|
|
|
|
|
|
|
|
|
|
|
BMA245 | 22,540 | 6,600 | 2 | 4,140 | 7,040 | 18 | 457 | 60 | 18.5 | 45 | 13.5 |
|
|
|
|
|
|
|
|
|
|
|
|
BMA300 | 27,600 | 8,080 | 2 | 3,960 | 6,730 | 18 | 457 | 60 | 18.5 | 45 | 13.5 |
|
|
|
|
|
|
|
|
|
|
|
|
BMA365 | 33,580 | 9,840 | 3 | 6,210 | 10,560 | 18 | 457 | 60 | 18.5 | 45 | 13.5 |
|
|
|
|
|
|
|
|
|
|
|
|
BMA450 | 41,400 | 12,130 | 3 | 5,940 | 10,100 | 18 | 457 | 60 | 18.5 | 45 | 13.5 |
|
|
|
|
|
|
|
|
|
|
|
|
BMA510 | 46,920 | 13,740 | 4 | 8,280 | 14,080 | 18 | 457 | 60 | 18.5 | 45 | 13.5 |
|
|
|
|
|
|
|
|
|
|
|
|
BMA600 | 55,200 | 16,170 | 4 | 7,920 | 13,460 | 18 | 457 | 60 | 18.5 | 45 | 13.5 |
|
|
|
|
|
|
|
|
|
|
|
|
BMA710 | 65,320 | 19,130 | 5 | 9,450 | 16,070 | 18 | 457 | 60 | 18.5 | 45 | 13.5 |
*Standard molded fan guards allow for extended air throw; optional wire guards promote air diffusion
† Air throw data based on
‡ For EC motors, use 60 Hz capacity and airflow values (Units with EC motors operating at 50 Hz will not see a reduction in performance due to the electronic control of the motor)