Performance Data
Model BMG/BMF Hot Gas Defrost 60 Hz
|
| Capacity |
| Fan Data |
|
| Air Throw*† |
|
| ||||
| Model | 10°F TD | 6°C TD |
|
|
| Diameter | Extended | Diffused | ||||
| No. | CFM | m3h | (Std.) | (Opt.) | ||||||||
|
|
|
| ||||||||||
|
| BTUH | Watts |
|
|
| in. | mm | ft. | m | ft. | m | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Inch | BMG190 | 19,000 | 5,570 | 2 | 4,700 | 7,990 | 18 | 457 | 65 | 20 |
| 50 | 15 |
|
|
|
|
|
|
|
|
|
|
|
|
| |
BMG260 | 26,000 | 7,620 | 2 | 4,500 | 7,650 | 18 | 457 | 65 | 20 |
| 50 | 15 | |
|
| ||||||||||||
Per |
|
|
|
|
|
|
|
|
|
|
|
|
|
BMG310 | 31,000 | 9,080 | 3 | 7,050 | 11,990 | 18 | 457 | 65 | 20 |
| 50 | 15 | |
|
|
|
|
|
|
|
|
|
|
|
|
| |
BMG390 | 39,000 | 11,420 | 3 | 6,750 | 11,480 | 18 | 457 | 65 | 20 |
| 50 | 15 | |
Fins |
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
BMG430 | 43,000 | 12,590 | 4 | 8,800 | 14,960 | 18 | 457 | 65 | 20 |
| 50 | 15 | |
6 |
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
BMG520 | 52,000 | 15,230 | 4 | 8,400 | 14,280 | 18 | 457 | 65 | 20 |
| 50 | 15 | |
|
| ||||||||||||
Inch | BMF165 | 16,500 | 4,830 | 2 | 4,900 | 8,330 | 18 | 457 | 65 | 20 |
| 50 | 15 |
|
|
|
|
|
|
|
|
|
|
|
|
| |
BMF220 | 22,000 | 6,440 | 2 | 4,650 | 7,910 | 18 | 457 | 65 | 20 |
| 50 | 15 | |
|
| ||||||||||||
Per |
|
|
|
|
|
|
|
|
|
|
|
|
|
BMF250 | 25,000 | 7,320 | 3 | 7,350 | 12,500 | 18 | 457 | 65 | 20 |
| 50 | 15 | |
|
|
|
|
|
|
|
|
|
|
|
|
| |
BMF330 | 33,000 | 9,670 | 3 | 6,975 | 11,860 | 18 | 457 | 65 | 20 |
| 50 | 15 | |
Fins |
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
BMF370 | 37,000 | 10,840 | 4 | 9,100 | 15,470 | 18 | 457 | 65 | 20 |
| 50 | 15 | |
4 |
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
BMF440 | 44,000 | 12,890 | 4 | 8,700 | 14,790 | 18 | 457 | 65 | 20 |
| 50 | 15 | |
|
|
Capacity Correction
Factors For Electric and
Hot Gas Defrost Units
Saturated |
|
|
|
|
| |
Suction | +20 | |||||
Temperature °F |
|
|
|
|
| |
|
|
|
|
|
| |
Saturated |
|
|
|
|
| |
Suction | ||||||
Temperature °C |
|
|
|
|
| |
|
|
|
|
|
| |
Multiply | 1.15 | 1.02 | 1.00 | 0.90 | 0.80 | |
Capacity By | ||||||
|
|
|
|
| ||
|
|
|
|
|
|
Model BMG/BMF Hot Gas Defrost 50 Hz‡
Model
Capacity | Fan Data |
|
| Air Throw*† |
| |||
10°F TD | 6°C TD |
|
| Diameter | Extended | Diffused | ||
CFM | m3h | (Std.) | (Opt.) | |||||
| ||||||||
BTUH | Watts |
|
|
| in. mm ft. m | ft. m |
4 Fins Per Inch 6 Fins Per Inch
BMG190 | 16,652 | 4,880 | 2 | 4,230 | 7,190 | 18 | 457 | 60 | 18.5 | 45 | 13.5 |
|
|
|
|
|
|
|
|
|
|
|
|
BMG260 | 22,724 | 6,660 | 2 | 4,050 | 6,890 | 18 | 457 | 60 | 18.5 | 45 | 13.5 |
|
|
|
|
|
|
|
|
|
|
|
|
BMG310 | 27,140 | 7,950 | 3 | 6,345 | 10,790 | 18 | 457 | 60 | 18.5 | 45 | 13.5 |
|
|
|
|
|
|
|
|
|
|
|
|
BMG390 | 34,132 | 10,000 | 3 | 6,075 | 10,330 | 18 | 457 | 60 | 18.5 | 45 | 13.5 |
|
|
|
|
|
|
|
|
|
|
|
|
BMG430 | 37,628 | 11,020 | 4 | 7,920 | 13,460 | 18 | 457 | 60 | 18.5 | 45 | 13.5 |
|
|
|
|
|
|
|
|
|
|
|
|
BMG520 | 45,448 | 13,310 | 4 | 7,560 | 12,850 | 18 | 457 | 60 | 18.5 | 45 | 13.5 |
BMF165 | 14,444 | 4,230 | 2 | 4,410 | 7,500 | 18 | 457 | 60 | 18.5 | 45 | 13.5 |
|
|
|
|
|
|
|
|
|
|
|
|
BMF220 | 19,228 | 5,630 | 2 | 4,185 | 7,120 | 18 | 457 | 60 | 18.5 | 45 | 13.5 |
|
|
|
|
|
|
|
|
|
|
|
|
BMF250 | 21,896 | 6,410 | 3 | 6,615 | 11,250 | 18 | 457 | 60 | 18.5 | 45 | 13.5 |
|
|
|
|
|
|
|
|
|
|
|
|
BMF330 | 28,888 | 8,460 | 3 | 6,278 | 10,670 | 18 | 457 | 60 | 18.5 | 45 | 13.5 |
|
|
|
|
|
|
|
|
|
|
|
|
BMF370 | 32,384 | 9,490 | 4 | 8,190 | 13,920 | 18 | 457 | 60 | 18.5 | 45 | 13.5 |
|
|
|
|
|
|
|
|
|
|
|
|
BMF440 | 38,456 | 11,260 | 4 | 7,830 | 13,310 | 18 | 457 | 60 | 18.5 | 45 | 13.5 |
|
|
|
|
|
|
|
|
|
|
|
|
*Standard molded fan guards allow for extended air throw; optional wire guards promote air diffusion
† Air throw data based on
‡ For EC motors, use 60 Hz capacity and airflow values (Units with EC motors operating at 50 Hz will not see a reduction in performance due to the electronic control of the motor)