Performance Data
Model GLC Hot Gas Defrost 60 Hz
|
| Capacity |
| Fan Data |
| ||
| Model | 10°F TD | 6°C TD |
|
|
|
|
| No. | CFM | m3H | ||||
|
| ||||||
|
| BTUH | Watts |
|
|
|
|
| GLC035 | 3,500 | 1,025 | 1 | 700 |
| 1,189 |
| GLC040 | 4,000 | 1,170 | 1 | 700 |
| 1,189 |
| GLC047 | 4,700 | 1,380 | 1 | 650 |
| 1,104 |
Inch | GLC065 | 6,500 | 1,900 | 2 | 1,400 |
| 2,379 |
GLC075 | 7,500 | 2,200 | 2 | 1,300 |
| 2,209 | |
GLC090 | 9,000 | 2,640 | 2 | 1,300 |
| 2,209 | |
Per |
| ||||||
GLC120 | 12,000 | 3,520 | 3 | 2,100 |
| 3,568 | |
6 Fins | GLC140 | 14,000 | 4,100 | 3 | 1,950 |
| 3,313 |
GLC160 | 16,000 | 4,690 | 4 | 2,600 |
| 4,418 | |
| GLC180 | 18,000 | 5,280 | 4 | 2,600 |
| 4,418 |
| GLC200 | 20,000 | 5,860 | 5 | 3,250 |
| 5,522 |
| GLC240 | 24,000 | 7,030 | 6 | 3,900 |
| 6,627 |
| GLC280 | 28,000 | 8,200 | 6 | 3,900 |
| 6,627 |
| GLC041 | 4,100 | 1,200 | 1 | 690 |
| 1,172 |
Inch | GLC068 | 6,800 | 2,000 | 2 | 1,380 |
| 2,345 |
GLC080 | 8,000 | 2,340 | 2 | 1,380 |
| 2,345 | |
Per | GLC102 | 10,200 | 2,990 | 3 | 2,170 |
| 3,687 |
GLC136 | 13,600 | 3,990 | 4 | 2,760 |
| 4,690 | |
Fins |
| ||||||
GLC170 | 17,000 | 4,980 | 5 | 3,450 |
| 5,862 | |
4 | GLC204 | 20,400 | 5,980 | 6 | 4,140 |
| 7,035 |
|
| ||||||
| GLC235 | 23,500 | 6,880 | 6 | 4,140 |
| 7,035 |
Model GLC Hot Gas Defrost 50 Hz †
|
| Capacity |
| Fan Data |
| ||
| Model | 10°F TD | 6°C TD |
|
|
|
|
| No. | CFM | m3H | ||||
|
| ||||||
|
| BTUH | Watts |
|
|
|
|
| GLC035 | 3,325 | 974 | 1 | 630 |
| 1,070 |
| GLC040 | 3,800 | 1,113 | 1 | 630 |
| 1,070 |
| GLC047 | 4,465 | 1,308 | 1 | 586 |
| 995 |
Inch | GLC065 | 6,175 | 1,809 | 2 | 1,260 |
| 2,142 |
GLC075 | 7,125 | 2,087 | 2 | 1,170 |
| 1,989 | |
|
| ||||||
Per | GLC090 | 8,550 | 2,504 | 2 | 1,170 |
| 1,989 |
GLC120 | 11,400 | 3,339 | 3 | 1,891 |
| 3,213 | |
6 Fins | GLC140 | 1,950 | 3,313 | 3 | 1,756 |
| 2,984 |
GLC160 | 2,600 | 4,418 | 4 | 2,341 |
| 3,978 | |
| GLC180 | 2,600 | 4,418 | 4 | 2,341 |
| 3,978 |
| GLC200 | 3,250 | 5,522 | 5 | 2,927 |
| 4,973 |
| GLC240 | 3,900 | 6,627 | 6 | 3,512 |
| 5,967 |
| GLC280 | 3,900 | 6,627 | 6 | 3,512 |
| 5,967 |
| GLC041 | 690 | 1,172 | 1 | 621 |
| 1,056 |
Inch | GLC068 | 1,380 | 2,345 | 2 | 1,243 |
| 2,111 |
GLC080 | 1,380 | 2,345 | 2 | 1,243 |
| 2,111 | |
Per | GLC102 | 2,170 | 3,687 | 3 | 1,954 |
| 3,320 |
GLC136 | 2,760 | 4,690 | 4 | 2,485 |
| 4,223 | |
Fins |
| ||||||
GLC170 | 3,450 | 5,862 | 5 | 3,107 |
| 5,279 | |
4 |
|
|
|
|
|
|
|
GLC204 | 4,140 | 7,035 | 6 | 3,728 |
| 6,334 | |
|
| ||||||
| GLC235 | 4,140 | 7,035 | 6 | 3,728 |
| 6,334 |
†For EC motors, use 60 Hz capacity and airflow values (Units with EC motors operating at 50 Hz will not see a reduction in performance due to the electronic
control of the motor)
Capacity Correction Factors For Electric and Hot Gas Defrost Units
Saturated Suction | +20 | ||||
Temperature °F |
|
|
|
| |
Saturated Suction | |||||
Temperature °C | |||||
|
|
|
| ||
Multiply Capacity | 1.15 | 1.04 | 1.00 | 0.90 | |
By | |||||
|
|
|
|
NOTE: When using the hot gas units with a hot gas loop drain pan on 0°F applications and below, an insulated drain pan is required.