2.Freezers

Display

 

 

 

 

 

 

 

 

°C=Celsius; °F=Fahrenheit. WARNING: When

 

°C = Celsius

 

 

 

 

Temperature

the measurement unit is changed the SET

 

 

 

 

CF

point and the values of the parameters Hy,

Pr2

°F

°F

°F

°F

measurement unit

 

LS, US, Ot, ALU and ALL have to be checked

 

=Fahrenheit

 

 

 

 

 

 

 

 

 

 

 

and modified if necessary

 

 

 

 

 

Defrost

 

 

 

 

 

 

 

 

 

 

EL = electric

 

 

 

tdF

Defrost type

EL = electrical heater; in = hot gas

Pr2

defrost / in

EL

EL

EL

= hot gas

 

 

 

 

 

 

 

 

 

 

 

defrost

 

 

 

 

 

(-50÷50 °C/ -58÷122°F) (Enabled only when

 

 

 

 

 

dtE

Defrost termination

EdF=Pb) sets the temperature measured by

Pr1

-58~122

65

65

38

temperature

the evaporator probe, which causes the end

 

 

 

 

 

 

 

 

of defrost

 

 

 

 

 

IdF

Interval between

(0÷120h) Determines the time interval

Pr1

0 ~ 120

6

6

6

defrost cycles

between the beginning of two defrost cycles

hours

 

 

 

 

 

 

 

(0÷255min) When P2P = n, (not evaporator

 

 

 

 

 

 

(Maximum) length

probe: timed defrost) it sets the defrost

 

0 ~ 255

 

 

 

MdF

duration, when P2P = y (defrost end based

Pr2

40

40

60

for defrost

minutes

 

on temperature) it sets the maximum

 

 

 

 

 

 

 

 

 

 

 

 

 

length for defrost

 

 

 

 

 

 

 

(0÷120 min) time interval between reaching

 

 

 

 

 

 

 

defrost termination temperature and the

 

 

 

 

 

Fdt

Drip time

restoring of the control’s normal operation.

Pr1

0 ~ 255

2

2

0

This time allows the evaporator to eliminate

minutes

 

 

 

 

 

 

 

 

water drops that might have formed due

 

 

 

 

 

 

 

to defrost

 

 

 

 

 

Fans

(XR60CX only)

 

 

 

 

 

 

Fnd

Fans delay after

(0÷255min) Interval between end of defrost

Pr1

0 ~ 255

2

2

Not

defrost

and evaporator fans start

minutes

Applicable

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature

(0÷59°C; Fct=0 function disabled). If the

 

 

 

 

 

 

difference of temperature between the

 

 

 

 

 

 

differential

 

 

 

 

Not

Fct

evaporator and the room probes is more

Pr2

0~90

10

10

avoiding short

Applicable

 

than the value of the Fct parameter, the

 

 

 

 

 

cycles of fans

 

 

 

 

 

 

fans are switched on

 

 

 

 

 

 

 

 

 

 

 

 

 

Fans stop

(-50÷50°C/122°F) setting of temperature,

 

 

 

 

Not

FSt

detected by evaporator probe, above

Pr1

-58~122

35

35

temperature

Applicable

 

which fans are always OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Alarms

 

 

 

 

 

 

 

 

 

(Ab; rE) Ab= absolute temperature: alarm

 

 

 

 

 

 

 

temperature is given by the ALL or ALU

 

rE = relative

 

 

 

ALC

Temperature alarms

values. rE = temperature alarms are

Pr2

to set point

Ab

Ab

Ab

configuration

referred to the set point. Temperature alarm

Ab =

 

 

 

 

 

 

 

is enabled when the temperature exceeds

 

absolute

 

 

 

 

 

the “SET+ALU” or “SET-ALL” values

 

 

 

 

 

 

MAXIMUM

(SET÷110°C; SET÷230°F) when this

 

 

 

 

 

ALU

temperature is reached the alarm is

Pr2

ALL~ 302

38

50

50

temperature alarm

 

enabled, after the “ALd” delay time

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum

-50.0 ÷ SET°C; -58÷230°F when this

 

 

 

 

 

ALL

temperature is reached the alarm is

Pr2

-58~ ALu

-25

15

30

temperature alarm

 

enabled, after the “ALd” delay time

 

 

 

 

 

 

 

 

 

 

 

 

ALARM SIGNALS

Message

Cause

Outputs

 

 

 

 

Room probe

Compressor output

“P1”

according to par. “Con” and

failure

 

“COF”

 

 

 

 

 

“P2”

Evaporator probe

Defrost end is timed

failure

 

 

 

 

 

“HA”

Maximum

Outputs unchanged.

temperature alarm

 

 

 

 

 

Message

Cause

Outputs

 

 

 

“LA”

Minimum

Outputs unchanged.

temperature alarm

 

 

 

 

 

“dA”

Door open

Compressor and fans

restarts

 

 

“EA”

External alarm

Output unchanged.

 

 

 

Reprinted with permission from Dixell.

10

Page 10
Image 10
Heatcraft Refrigeration Products H-IM-82B installation and operation guide Alarm Signals, Message Cause Outputs