Heatcraft Refrigeration Products H-IM-82B Freezers, Default Parameter Settings, Menu/User

Models: H-IM-82B

1 20
Download 20 pages 1.31 Kb
Page 9
Image 9
Main Functions

Main Functions

HOW TO SEE THE SETPOINT

1.Push and immediately release the SET key: the display will show the Set point value.

HOW TO CHANGE THE SETPOINT

1.Push the SET key for more than 2 seconds to change the Set point value;

2.The value of the set point will be displayed and the LED starts blinking;

3.To change the Set value push the UP or DOWN arrows within 10s.

4.To memorise the new set point value push the SET key again or wait 10s.

HOW TO START A MANUAL DEFROST

Push the DEF key for more than 2 seconds and a manual defrost will start.

HOW TO CHANGE a parameter value

To change the parameter’s value operate as follows:

1.Use “UP” or “DOWN” to change its value.

2.Press “SET” to store the new value and move to the following parameter.

To exit: Press SET + UP or wait 15s without pressing a key.

NOTE: the set value is stored even when the procedure is exited by waiting the time-out to expire.

THE HIDDEN MENU

The hidden menu Includes all the parameters of the instrument.

HOW TO ENTER THE HIDDEN MENU

1.Enter the Programming mode by pressing the Set + DOWN key for 3s (LED 1 and start blinking).

2.When a parameter is displayed keep pressed the Set + DOWN for more than 7s. The Pr2 label will be displayed immediately followed from the HY parameter.

NOW YOU ARE IN THE HIDDEN MENU.

3.Select the required parameter.

4.Press the “SET” key to display its value (Now only the LED is blinking).

5.Use UP or DOWN to change its value.

6.Press “SET” to store the new value and move to the following parameter.

To exit: Press SET + UP or wait 15s without pressing a key.

NOTE: the set value is stored even when the procedure is exited by waiting the time-out to expire.

HOW TO SEE THE alarm duration and MAX (min)

TEMPERATURE

If the alarm LED is on, an alarm has taken place.

To see the kind of alarm, the max (min) reached temperature and alarm duration do as follows:v

1.Push the Up or Down key.

2.On the display the following message is shown:: “HAL” for high temperature alarm (“LAL” for the minimum allarm), followed by the Maximum (minimum) temperature.

Then the “tiM” (tiMe) message is displayed, followed by the “Duration” in h.mm.

3.Then the instrument displays the temperature once again.

NOTE1: if an alarm is still occurring the “tim” shows the partial duration.

NOTE2: the alarm is recorded when the temperature come back to normal values

HOW TO RESET a recorded alarm OR ONE THAT IS STILL OCCURRING

1.Hold the SET key pressed for more than 3s, while the recorded alarm is displayed. (the rSt message will be displayed)

2.To confirm the operation, the “rSt” message starts blinking and the normal temperature will be displayed

2. Freezers

DEFAULT PARAMETER SETTINGS

 

 

 

Menu/User

Possible

Default Settings

Label

Characteristic

Description

 

 

 

 

 

 

Level

Settings

Low

Medium

High

 

 

 

 

 

 

 

 

Temp.

Temp.

Temp.

 

 

 

 

 

 

 

 

Regulation

 

 

 

 

 

 

SEt

Set Point

 

 

LS ~ US

-10

34

38

 

 

(0,1 ÷ 25,5°C / 1÷255 °F) Intervention

 

 

 

 

 

 

 

differential for set point. Compressor

 

 

 

 

 

Hy

Differential

Cut IN is Set Point + differential (Hy).

Pr1

1~ 45

3

3

3

 

 

Compressor Cut OUT is when the

 

 

 

 

 

 

 

temperature reaches the set point

 

 

 

 

 

LS

Minimum set point

(- 50°C÷SET/-58°F÷SET): Sets the minimum

Pr2

-67 ~ SET

-23

25

33

value for the set point..

US

Maximum set point

(SET÷110°C/ SET÷230°F). Set the maximum

Pr2

SET ~ 302F

37

40

45

value for set point.

Ot

Thermostat probe

(-12.0÷12.0°C; -120÷120°F) allows to adjust

Pr2

-21~21

0

0

0

calibration

possible offset of the thermostat probe

 

 

 

 

 

 

 

 

(0÷255min) This function is enabled at

 

 

 

 

 

OdS

Outputs activation

the initial start up of the instrument and

Pr2

0 ~ 255

0

0

0

delay at start up

inhibits any output activation for the period

minutes

 

 

 

 

 

 

 

of time set in the parameter

 

 

 

 

 

AC

Anti-short cycle

(0÷50 min) minimum interval between the

Pr2

0 ~ 50

4

4

4

delay

compressor stop and the following restart

minutes

 

 

 

 

 

 

Compressor OFF

(0÷255 min) time during which the

 

 

 

 

 

 

compressor is OFF in case of faulty

 

0 ~ 255

 

 

 

COF

time with faulty

Pr2

6

6

6

thermostat probe. With COF=0

minutes

 

probe

 

 

 

 

 

compressor is always active

 

 

 

 

 

 

 

 

 

 

 

 

Page 9
Image 9
Heatcraft Refrigeration Products H-IM-82B Freezers, Default Parameter Settings, Menu/User, Possible, Default Settings