OPTIONAL WIRING

When wiring to additional standard fixture only: Strip the motion sensor's red wire and connect to the standard light's black wire.Connect all white wires together. Total fixture ratings must not exceed 360 Watts (3.0 A.).

NOTE: All wiring between fixtures should be run in accordance with the National Electrical Code (Canadian Electrical Code in Canada) through conduit or another acceptable means. Contact a qualified electrician if there is any question as to the suitability of the system.

This fixture is provided with a sensor rated for 360 Watts. Since the fixture is only rated 100 Watts, 260 Watts of additional load may be controlled by this sensor.

When determining what a fixture is rated for, do not simply look at the rating on the lamp in the fixture. Look at the marking which specifies the maximum lamp watt- age for which the fixture is suitable.

Once you have selected the fixtures to be connected and determined their maximum ratings, add these ratings up. For instance, if you have 3 fixtures rated 100 Watts, 150 Watts, and 75 Watts re- spectively, you have a total load of 325 Watts.

MasterSlave

BLACK

BLACK

BLACK

 

 

RED

RED

 

 

WHITE

WHITE

WHITE

BLACK

 

 

 

(Standard)

 

WHITE

 

 

 

Wiring to Motion Light &

Wiring to Control One Motion Sensing

Standard Fixture

Lantern (Slave) from Another (Master)