Heatmaster 100 N Technical Specification, Maximum Operating Conditions, Burner Chamber Plate

Models: 150 JUMBO 100 N HM 60 N 70 N

1 30
Download 30 pages 43.39 Kb
Page 6
Image 6
MAXIMUM OPERATING CONDITIONS

MAXIMUM OPERATING CONDITIONS

Maximum service pressure (tank full of water)

-Primary circuit: 3 bar

-Secondary circuit: 10 bar

Test pressure (tank full of water)

-Primary circuit: 4.5 bar

-Secondary circuit: 13 bar

Operating temperature

- Maximum temperature: 90 °C

Water quality

Chlorures: < 150 mg/l (304)

<2000 mg/l (Duplex)

6 ph 8

TECHNICAL SPECIFICATION

BURNER CHAMBER PLATE

The burner chamber plate has 4 threads (M 10 x 20) for attaching the burner. It is protected from heat by a blanket insulation.

5xØ6.5(M8)

Ø28

Ø130

60•6 ≤ ph ≥ 8

60TECHNICAL SPECIFICATION

60 60

DOMESTIC HOT WATER PERFORMANCES

 

 

HM 60 N

HM 60 N

HM 70 N

HM 70 N

HM 100 N

HM 100 N

HM 150

 

 

BM 101

BG 2000-S/60

BM 101

BG 2000-S/70

BM 101

BG 2000-S/100

JUMBO

Peak delivery at 40 °C

L/10’

474

474

646

646

905

905

1504

Peak delivery at 45 °C

L/10’

378

378

543

543

777

777

1289

Peak delivery at 60 °C

L/10’

245

245

346

346

514

514

870

Peak delivery at 70 °C

L/10’

193

193

268

268

343

343

700

Peak delivery at 80 °C

L/10’

135

135

207

207

258

258

540

 

 

 

 

 

 

 

 

 

Peak delivery at 40 °C

L/60’

1942

1942

2133

2133

3172

3172

4828

Peak delivery at 45 °C

L/60’

1656

1656

1794

1794

2680

2680

4138

Peak delivery at 60 °C

L/60’

1106

1106

1219

1219

1813

1813

2864

Peak delivery at 70 °C

L/60’

681

681

971

971

1226

1226

2131

Peak delivery at 80 °C

L/60’

499

499

636

636

893

893

1362

 

 

 

 

 

 

 

 

 

Continuous delivery at 40 °C

L/h

1835

1835

1835

1835

2776

2776

3989

Continuous delivery at 45 °C

L/h

1573

1573

1573

1573

2379

2379

3419

Continuous delivery at 60 °C

L/h

1101

1101

1067

1067

1665

1665

2393

Continuous delivery at 70 °C

L/h

791

791

918

918

1104

1104

1718

Continuous delivery at 80 °C

L/h

455

455

580

580

804

804

987

 

 

 

 

 

 

 

 

 

Reheat time at 60 °C

min

9

9

16

16

13

13

17

 

 

 

 

 

 

 

 

 

GENERAL FEATURES

 

 

HM 60 N

HM 70 N

HM 100 N

HM 150

 

 

 

 

 

JUMBO

Maximum Input

kW

69.9

69.9

107.0

154.0

Maximum Output

kW

62.5

63.0

96.8

139.1

Maintenance loss at 60 °C as rated value

%

0.57

0.60

0.65

0.52

Total capacity

L

162

239

330

645

Primary circuit capacity

L

82

108

130

245

Heating connection

Ø

11/2

11/2

11/2

DN 50

Hot water connection

Ø

3/4”

1”

1”

2”

Hot water tank heat exchange surface

m2

2.46

3.14

3.95

5.30

Weight empty

Kg

220

270

320

530

Pressure drop primary circuit

mbar

54

46

83

120

 

 

 

 

 

 

5