Engineering Guideline |
Fieldbus Slave Modules
|
| Item |
|
| |
Fieldbus system |
| DeviceNet | |||
General |
| Type | DeviceNet slave module for use with | ||
| standard I/O modules of | standard I/O modules of | |||
|
|
| |||
|
|
|
|
| |
Function |
| Max. number of | 2 (2nd rack connected via | 2 (2nd rack connected via | |
|
|
|
|
| |
|
| Max. number of modules | 16 | 16 | |
|
| Node address range | 1 - 99 | 1 - 63 | |
|
| Max. number of I/O's (with | 1024 | 1024 | |
|
| 64 point I/O modules | |||
|
|
|
| ||
|
| Max. input and output data | 208 words | 208 words | |
|
|
|
|
| |
|
| In data update cycle time | 5ms | 5ms | |
|
| 9.6 kbps | 1200m | - | |
|
| 19.2 kbps | 1200m | - | |
|
| 45.45 kbps | 1200m | - | |
|
| 93.75 kbps | 1200m | - | |
Max. segment |
| 125 kbps | - | 500m | |
| 187.5 kbps | 1000m | - | ||
lenght (at data |
| ||||
| 250 kbps | - | 250m | ||
transfer rate). |
| ||||
| 500 kbps | 400m | 100m | ||
|
| ||||
|
| 1500 kbps | 200m | - | |
|
| 3 Mbps | 100m | - | |
|
| 6 Mbps | 100m | - | |
|
| 12 Mbps | 100m | - | |
Internal current consumption (5V) | Approx. 600mA | Approx. 600mA | |||
I/O assignment |
| fixed at | fixed at | ||
External connection | 9 pin | ||||
External wiring |
| Double shielded twisted pair cables | DeviceNetTM dedicated cable | ||
| according to Profibus specification | ||||
|
|
|
| ||
Self diagnosis |
| System ROM/RAM check, | System ROM/RAM check, | ||
| |||||
|
|
| |||
|
|
| |||
|
|
| This file can either be downloaded | This file can either be downloaded | |
File for configuration | from the web (www.hitachi- | from the web (www.hitachi- | |||
|
|
| ds.com/sub/info/updates) or received | ds.com/sub/info/updates) or received | |
|
|
| directly from Hitachi Europe | directly from Hitachi Europe | |
Configurator software | Profibus configurator software, | DeviceNet configurator RSNetworx | |||
and dedicated interface adapter | |||||
|
|
|
8