Engineering Guideline

EH-150 Series PLC

Fieldbus Slave Modules

 

 

Item

EH-IOCP

EH-IOCD

Fieldbus system

 

Profibus-DP

DeviceNet

General

 

Type

Profibus-DP slave module for use with

DeviceNet slave module for use with

 

standard I/O modules of EH-150 series

standard I/O modules of EH-150 series

 

 

 

 

 

 

 

 

Function

 

Max. number of base-racks

2 (2nd rack connected via EH-IOC)

2 (2nd rack connected via EH-IOC)

 

 

 

 

 

 

 

Max. number of modules

16

16

 

 

Node address range

1 - 99

1 - 63

 

 

Max. number of I/O's (with

1024

1024

 

 

64 point I/O modules

 

 

 

 

 

 

Max. input and output data

208 words

208 words

 

 

 

 

 

 

 

In data update cycle time

5ms

5ms

 

 

9.6 kbps

1200m

-

 

 

19.2 kbps

1200m

-

 

 

45.45 kbps

1200m

-

 

 

93.75 kbps

1200m

-

Max. segment

 

125 kbps

-

500m

 

187.5 kbps

1000m

-

lenght (at data

 

 

250 kbps

-

250m

transfer rate).

 

 

500 kbps

400m

100m

 

 

 

 

1500 kbps

200m

-

 

 

3 Mbps

100m

-

 

 

6 Mbps

100m

-

 

 

12 Mbps

100m

-

Internal current consumption (5V)

Approx. 600mA

Approx. 600mA

I/O assignment

 

fixed at CPU-Slot

fixed at CPU-Slot

External connection

9 pin D-sub, female

5-pole DeviceNet connector

External wiring

 

Double shielded twisted pair cables

DeviceNetTM dedicated cable

 

according to Profibus specification

 

 

 

 

Self diagnosis

 

System ROM/RAM check,

System ROM/RAM check,

 

watch-dog timer check

watch-dog timer check

 

 

 

 

 

 

GSD-file, File name:Hita049d.gsd.

EDS-file, File name: Absdev.eds.

 

 

 

This file can either be downloaded

This file can either be downloaded

File for configuration

from the web (www.hitachi-

from the web (www.hitachi-

 

 

 

ds.com/sub/info/updates) or received

ds.com/sub/info/updates) or received

 

 

 

directly from Hitachi Europe

directly from Hitachi Europe

Configurator software

Profibus configurator software,

DeviceNet configurator RSNetworx

Order-Number: PBDP-M-CONF

and dedicated interface adapter

 

 

 

8