3–36

“B” Group: Fine-Tuning Functions

Software Lock

Mode

Configuring Drive

Parameters

 

 

The software lock function keeps personnel from accidentally changing parameters in the inverter memory. Use B031 to select from various protection levels.

The table below lists all combinations of B031 option codes and the ON/OFF state of the [SFT] input. Each Check or Ex indicates whether the corresponding parameter(s) can be edited. The Standard Parameters column below lists Low and High level access for some lock modes. These refer to the parameter tables throughout this chapter, each of which includes a column titled Run Mode Edit as shown to the right. The two marks (Check or Ex ) under the “Lo Hi” subtitle indicate whether Low-level and/or High-level access

applies to each parameter as defined in the table below. In some lock modes, you can edit only F001 and the Multi-speed parameter group that includes A020, A220, A320, A021–A035, and A038 (Jog). However, it does not include A019, Multi-speed operation selection. The editing access to B031 itself is unique, and is specified in the right-most two columns below.

B031[SFT]Standard ParametersF001 and

 

B031

Multi-speed

 

Lock

Intelligent

 

 

 

 

 

 

 

 

 

 

 

Mode

Input

Stop

Run

Stop or Run

Stop

 

Run

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00

OFF

Low-level

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

01

OFF

Low-level

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

02

(ignored)

 

 

 

 

 

 

 

 

 

03

(ignored)

 

 

 

 

 

 

 

 

 

10

(ignored)

High-level

 

 

 

 

 

 

 

 

 

NOTE: Since the software lock function B031 is always accessible when the motor is stopped, this feature is not the same as password protection used in other industrial control devices.

 

“B” Function

Run

 

Defaults

 

 

 

 

 

 

 

 

Mode

 

 

 

 

Units

SRW Display

Func.

 

 

 

–FE

–FU

 

–F

 

 

 

Edit

 

Name

 

Description

 

 

 

 

Code

 

Lo Hi

(CE)

(UL)

 

(Jpn)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B031

Software lock mode

Prevents parameter changes

✘ ✔

01

01

 

01

>b031 S-LOCK

 

 

selection

in five options:

 

 

 

 

 

 

Mode

MD1

 

 

 

 

 

 

 

 

 

 

 

00

Low-level access, [SFT]

 

 

 

 

 

 

 

 

 

 

 

input blocks all edits

 

 

 

 

 

 

 

 

 

 

01

Low-level access, [SFT]

 

 

 

 

 

 

 

 

 

 

 

input blocks edits

 

 

 

 

 

 

 

 

 

 

 

(except F001 and Multi-

 

 

 

 

 

 

 

 

 

 

 

speed parameters)

 

 

 

 

 

 

 

 

 

 

02

No access to edits

 

 

 

 

 

 

 

 

 

 

03

No access to edits except

 

 

 

 

 

 

 

 

 

 

 

F001 and Multi-speed

 

 

 

 

 

 

 

 

 

 

 

parameters

 

 

 

 

 

 

 

 

 

 

10

High-level access,

 

 

 

 

 

 

 

 

 

 

 

including B031

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: To disable parameter editing when using B031 lock modes 00 and 01, assign the [SFT] function to one of the intelligent input terminals. See “Software Lock” on page 4–25.