6–3

SJ300 Inverter

Troubleshooting The table below lists typical symptoms and the corresponding solution(s).

Tips
Symptom/conditionProbable CauseSolution

 

 

 

 

 

 

 

 

 

 

 

 

 

Is the frequency command source

Make sure the parameter

 

 

 

A001 parameter setting correct?

setting A001 is correct.

 

 

 

Is the Run command source A002

Make sure the parameter

 

 

 

parameter setting correct?

setting A002 is correct.

 

 

 

 

 

 

 

 

Is power being supplied to terminals

Check terminals [R], [S], and

 

 

 

[R], [S], and [T] ([L1], [L2], and

[T] ([L1], [L2], and [L3]), then

 

 

 

[L3])? If so, the POWER lamp should

[U], [V], and [W] ([T1], [T2],

 

 

 

be ON.

and [T3]).

 

 

 

 

Turn ON the power supply or

 

 

 

 

check fuses.

 

 

 

 

 

 

 

 

Is there an error code EXX.X

Press the Func. key and deter-

 

 

The inverter

displayed?

mine the error type. Eliminate

 

 

 

the error cause, then clear the

 

 

outputs U, V, W

 

error (Reset).

 

 

are not supplying

 

 

The motor

 

Are the signals to the intelligent input

Verify the terminal functions

 

voltage.

will not run.

 

terminals correct?

for C001 - C008 are correct.

 

 

 

Is the Run Command active?

Turn ON Run command

 

 

 

 

enable.

 

 

 

Is the [FW] terminal (or [RV])

Supply 24V to [FW] or [RV]

 

 

 

connected to P24 (via switch, etc.)

terminal, if configured.

 

 

 

 

 

 

 

 

Has the frequency setting for F001

Set the parameter for F001 to a

 

 

 

been set greater than zero?

safe, non-zero value.

 

 

 

Are the control circuit terminals [H],

If the potentiometer is the

 

 

 

[O], and [L] connected to the potenti-

frequency setting source, verify

 

 

 

ometer?

voltage at [O] > 0V.

 

 

 

 

 

 

 

 

Is the RS (reset) function or FRS (free-

Turn OFF the command(s).

 

 

 

run stop) function ON?

 

 

 

 

 

 

 

 

Inverter outputs

Is the motor load too heavy?

Reduce load or test the motor

 

 

U, V, W are

 

independently of the load.

 

 

supplying voltage.

 

 

 

 

 

 

 

 

 

 

Are the connections of output termi-

Make connections according to

 

 

 

nals [U/T1], [V/T2], and [W/T3]

the phase sequence of the

 

 

 

correct?

motor. In general:

The direction of the motor is

Is the phase sequence of the motor

FWD = U-V-W, and REV=U-

forward or reverse with respect to

W-V.

 

reversed.

[U/T1],[V/T2], and [W/T3]?

 

 

 

 

 

 

 

 

 

 

 

 

 

Are the control terminals [FW] and

Use terminal [FW] for forward,

 

 

 

[RV] wired correctly?

and [RV] for reverse.

 

 

 

Is parameter F004 properly set?

Set motor direction in F004.

 

 

 

 

 

Troubleshooting Maintenance and