3–60

“C” Group: Intelligent Terminal Functions

Analog SignalCalibration

Settings

The functions in the following table configure the signals for the analog output terminals. Note that these settings do not change the current/voltage or sink/source characteristics – only the zero and span (scaling) of the signals.

 

 

 

 

 

 

 

 

 

 

“C” Function

Run

 

Defaults

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mode

 

 

 

 

Units

SRW Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Func.

 

 

 

 

 

 

 

 

 

Edit

–FE

–FU

 

–FR

 

 

 

 

 

 

 

 

Name

Description

 

 

 

 

 

 

 

 

Code

 

 

 

 

 

Lo Hi

(CE)

(UL)

 

(Jpn)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C081

[O] input span calibra-

Range is 0 to 65530

✔ ✔

Factory-calibrated

>C081 O-ADJUST

 

 

 

 

tion

 

 

 

 

 

 

 

TOP

02119

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C082

[OI] input span calibra-

Range is 0 to 65530

✔ ✔

Factory-calibrated

>C082 OI-ADJUST

 

 

 

 

tion

 

 

 

 

 

 

 

TOP

02512

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C083

[O2] input span calibra-

Range is 0 to 65530

✔ ✔

Factory-calibrated

>C083 O2-ADJUST

 

 

 

 

tion

 

 

 

 

 

 

 

TOP

02818

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DriveConfiguring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameters

 

C085

Thermistor input tuning

Range is 0.0 to 1000

✔ ✔

105.0

105.0

 

105.0

>C085 THERM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ADJUST

0105.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C086

[AM] terminal offset

Range is 0.0 to 10.0V

✔ ✔

0.0

0.0

 

0.0

V

>C086 AM-MONITOR

 

 

 

 

tuning

 

 

 

 

 

 

 

OFFSET

00.0V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C087

[AMI] terminal meter

Range is 0.0 to 250%

✔ ✔

80.

80.

 

80.

%

>C087 AMI-MON

 

 

 

 

tuning

 

 

 

 

 

 

 

ADJUST

080

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C088

[AMI] terminal offset

Range is 0 to 20mA

✔ ✔

Factory-calibrated

mA

>C088 AMI-MON

 

 

 

 

tuning

 

 

 

 

 

 

 

OFFSET

04.0mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C121

[O] input zero calibra-

Range is 0 to 6553 (65530)

✔ ✔

Factory-calibrated

>C121 O-ADJUST

 

 

 

 

tion

 

 

 

 

 

 

 

ZERO

00000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C122

[OI] input zero calibra-

Range is 0 to 6553 (65530)

✔ ✔

Factory-calibrated

>C122 OI-ADJUST

 

 

 

 

tion

 

 

 

 

 

 

 

ZERO

00000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C123

[O2] input zero calibra-

Range is 0 to 6553 (65530)

✔ ✔

Factory-calibrated

>C123 O2-ADJUST

 

 

 

 

tion

 

 

 

 

 

 

 

ZERO

03622

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: Settings C081, C082, C083, C121, C122, C123 are factory-calibrated for each inverter.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Do not change these settings unless absolutely necessary. Note that if you restore factory

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

defaults for all parameters, these settings will not change.