HC24EA SERIES ELECTRIC COUNTERTOP CONVECTION STEAMERS
ELECTRICAL CONNECTION
WARNING: ELECTRICAL AND GROUNDING
CONNECTIONS MUST COMPLY WITH AP-
PLICABLE PORTIONS
OF THE NATIONAL
ELECTRICAL
CODE AND/OR OTHER LOCAL
ELECTRICAL CODES.
The wiring diagram is located on the right side
panel as you face the steamer. This steamer is
hard wired.
Total Volts Hz Ph KW Per Phase Rated Amps Circuit Fuse
KW 3-Phase Amps per Line Single Size Size
L1-L2 L2-L3 L3-L1 L 1 L2 L3 Phase Amps** or
Circuit
Breaker
Size*
(Amps)
8.5 208 50/60 1 40.87 60 60
8.5 240 50/60 1 35.42 50 50
8.5 208 50/60 3 4.25 2.12 2.12 26.54 26.54 17.70 35 35
8.5 240 50/60 3 2.83 2.83 2.83 20.50 20.50 20.50 30 30
8.5 480 50/60 3 2.83 2.83 2.83 10.30 10.30 10.30 15 15
9.25 208 50/60 1 43.57 60 60
9.25 240 50/60 1 38.54 50 50
9.25 208 50/60 3 4.25 2.69 2.12 26.54 28.88 20.04 40 40
9.25 240 50/60 3 2.83 3.58 2.83 20.45 23.15 23.15 30 30
9.25 480 50/60 3 2.83 3.58 2.83 10.21 11.57 11.57 15 15
15 208 50/60 1 72.12 90 90
15 240 50/60 1 62.50 75 75
15 208 50/60 3 7.50 3.75 3.75 46.84 46.84 31.23 60 60
15 240 50/60 3 5.00 5.00 5.00 36.08 36.08 36.08 50 50
15 480 50/60 3 5.00 5.00 5.00 18.04 18.04 18.04 25 25
15.75 208 50/60 1 74.82 95 95
15.75 240 50/60 1 65.63 85 85
15.75 208 50/60 3 7.50 4.31 3.75 46.84 49.18 33.57 65 65
15.75 240 50/60 3 5.00 5.75 5.00 36.08 38.79 38.79 50 50
15.75 480 50/60 3 5.00 5.75 5.00 18.04 19.40 19.40 25 25
2002 National Electric Code
*Dual Element Time-Delay Fuse or Inverse Time Circuit Breaker
** Circuit Size (minimum) & Fuse/Circuit Breaker Size (maximum) compiled in accordance with the
National Electrical Code (ANSI/NFPA 70), 2002 Edition.