7
Operation / Test Procedure
1. Switch positions should remain in the “LINE” position under normal utility
power. The “OFF” position is generally not used. The “GEN” positions are used
when connecting circuits to your generator power source.
2. When testing and/or switching to generator power after a power outage,
ensure all switches are in the “LINE” position. (There is no need to turn off
any load center circuit breakers).
3. Plug your power cord set into your generator by aligning the male prongs with
the female terminals of your generator’s receptacle, push the connector in
and twist clockwise to lock (some connectors do not twist). Align the female
socket of the cord set into your EmerGen Switch, push it in and turn
clockwise to lock.
4. Move your generator outdoors before starting it up. Check to see that fluids
and fuel are adequate and start your generator according to the
manufacturer’s instructions.
5. At your EmerGen Switch, move one circuit to the “GEN” position, making a
note of how much wattage is used on the watt meter. While monitoring the
load, flip each circuit—one at a time—to the “GEN” position. You do not need
to go “in order” and you want to balance the loads so that both meters read
approximately the same. Do not switch on more loads than your generator
can supply.

Note: Wattage must not exceed the maximum printed on the meters.

Load Management
1. All circuits can be used simultaneously only if your generator has sufficient
wattage capacity. If an electrical load on the EmerGen Switch is exceeded by
it’s capacity, the mini-breaker may trip.
To Reset:
a. Eliminate the overload condition.
b. Move the switch with the tripped breaker to the “OFF” position.
c. Reset the breaker by pressing it in, making sure it stays in.
d. Move the switch back to the “GEN” position. It should now operate
properly. If it does not, you may need to contact an electrician or
qualified professional.