Basin and Cover
The basin should not be less than 18 inches in diameter and 24 inches deep.
Larger diameters are advisable in instances of increased pump capacity requirements:
The basin should be located such that all water flows into the basin due to gravity.
Outdoor installations should be at a sufficient depth to ensure protection from freezing.
Maintenance Tips
Every three or four months:
1) Clean the pump screen or inlet opening. If your sump collects the discharge
from an automatic washing machine, cleaning will be required more often.(Before
removing the pump be sure to disconnect the unit from electrical power; and
reconnect after completion of cleaning);
2) Pour enough water into the sump to cycle the pump and assure its proper
functioning.
Annually:
Remove and clean the pump.Clean the sump pit also.
5

WARNING

Before handling this pump, always disconnect

the power first.

This pump should only be serviced by a qualified person or a factory
trained person.

CAUTION

This instruction manual includes necessary items for installation, operation
and maintenance.
Read this manual carefully to ensure correct installation,
operation and maintenance.
Be sure to keep this instruction manual on hand for future reference.
Required Minimum
Pump Capacity Basin Diameter
up to 35 GPM 18"
over 35 GPM 24"
over 60 GPM 30"
over 100 GPM 36"
over 150 GPM 48"