iPGSM-COM Commercial Fire Communicator – Installation and Setup Guide

STEP 5 – Program the Communications Module

You must use the 7720P Programming tool to program the iPGSM-COM.

When using the 7720P Programming tool, the values given below are for most installations. Press the [#] key to accept the displayed default value (xxx) or enter the new value and press the [#] key for the next prompt. Use the [] key to scroll through a list of options.

1.

 

 

(no display)

 

 

Connect the 7720P.

 

 

 

 

 

 

 

 

 

2.

 

 

7720P PROGRAMMER

 

Press [#].

 

3.

 

 

 

 

Press [Shift] then [Y], then [#].

 

 

Strt Prog Mode? Y/N

 

 

 

 

 

 

 

 

4.

 

 

Program Device? Y/N

 

Press [Shift] then [Y], then [#].

 

5.

 

 

 

 

 

Enter number 01-99, then press [#].

 

 

Primary City ID

(??)

 

 

 

 

 

 

 

 

 

6.

 

 

Primary CS ID

(??)

 

Enter number 01-FE, then press [#].

 

7.

 

 

 

 

 

Enter number 0001-9999, then press [#].

 

 

Primary Sub ID

(????)

 

 

 

 

 

 

 

 

 

8.

 

 

Review? Y/N

 

 

Enter choice, then press [#]. Follow the prompts.

 

9.

 

 

 

 

Enter choice, then press [#]. Follow the prompts.

 

 

Create Password? Y/N

 

 

 

 

 

 

 

10.

 

 

Exit Prog Mode? Y/N

 

Press [Shift] then [Y], then press [#].

 

11.

 

 

 

 

 

 

 

DONE

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: If an error in programming occurs, set the factory defaults (see next topic) and reprogram the iPGSM-COM.

To exit the programming mode, press [N] in response to the "Review?" prompt. Then press [Y] to the "Exit Prog Mode?" prompt. Upon exiting, the root file is updated to log the changes made. A message is displayed telling the user that this step is being executed. When complete, the message "DONE" is displayed to indicate the file was successfully uploaded.

Note: If critical configuration changes were made, such as the mode of operation, the communications module will reset to ensure that the programming features are enabled.

If the file is not successfully uploaded, one of the following prompts will be displayed. Follow the steps shown below until the upload is successful.

 

Display

Description

What to do

 

 

 

Module is not yet initialized.

Wait for RSSI indicator LEDs to be lit.

 

Cannot Upload

 

 

Try Again? Y/N_

 

 

Press [Y].

 

 

 

 

 

 

 

Network problem, or you

Initiate the Force Server Update

 

Failed to Update

 

 

Root File!

 

answered "N" to "Cannot

Command by pressing the [0] key.

 

 

Upload Try Again?" prompt.

 

 

 

 

 

 

 

 

 

Setting Factory Defaults

To reset the programming options to factory-default values, at the "Exit Prog Mode?" prompt press [Shift] plus [ESC]. Note, setting the factory defaults will also erase any password that may have been entered.

Set Default?

Y/N_

Press [Y] to reset factory default values. Press [N] to cancel this function.

Press [Shift] then [Y], then [#]. The Create Password prompt appears, follow the prompts then exit.