Honeywell F118 Installation, When Installing This Product, Unpack Air Cleaner, Explosion Hazard

Models: F118

1 12
Download 12 pages 12.02 Kb
Page 4
Image 4
INSTALLATION

F118 IN-CEILING MEDIA AIR CLEANER

INSTALLATION

Explosion Hazard. WARNING

Explosion Hazard.

Can cause personal injury or equipment damage. Do not install or use the F118 Air Cleaner where there is any danger of a gas, vapor or dust explosion.

Do not install when explosion-proof electrical fixtures are specified.

Fire or Electric Shock Hazard. WARNING

Fire or Electric Shock Hazard.

Can cause personal injury or equipment damage. Turn off power source before installing or servicing air cleaner.

Do not use air cleaner in the ceilings of fire-resistant assemblies.

When Installing This Product . . .

Use the following procedure to remove the grille and all contents of the cabinet, including the CPZ modules and filters.

1.Remove the grille:

a.Remove the bolts from the hinge that hold the grille to the cabinet.

b.Remove the bolts and the spring-loaded plungers at the other end of the cabinet.

c.Set aside the grille.

2.Remove the filters:

a.Pre-filter is wrapped around the particulate filter. Two support rods in the center bay of the cabinet hold the particulate filter and the pre-filter in place. Push these rods apart and lift the filters out of the cabinet.

b.Two CPZ sorbent modules wrapped in plastic are located at either end of the cabinet. Tilt each module to lift it from the cabinet. Set aside both modules.

3.Remove the cabinet from the container.

4.Remove all shipping cardboard and containers inside and outside of the air cleaner components.

5.Inspect the packing material to ensure that no parts or papers are lost.

1.Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condi- tion.

2.Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.

3.Installer must be a trained, experienced service techni- cian.

4.After installation is complete, check out product opera- tion as provided in these instructions.

Unpack Air Cleaner

When Installing This Product . . . WARNING

Sharp Edges.

Can cause personal injury.

Wear protective gloves and handle air cleaner care- fully to avoid cuts from sharp metal edges.

The air cleaner is shipped assembled in a packing container. When unpacking, check that all air cleaner components are included.

1.Container:

Installation Instructions (1).

Support shoulders (8).

2.Assembled cabinet; consists of a cabinet frame and grille/door assembly:

Blower/motor assembly (1).

CPZ™ media module (2).

Particulate filter (1).

Pre-filter attachment clip (2).

Pre-filter (1).

The installer must supply the following additional items required for the installation:

1.Any external hardware such as extra nuts and bolts.

2.Wire, with a gauge strong enough to bear the weight of the air cleaner and long enough to reach from the con- necting points in the structural ceiling to the support shoulders on the air cleaner.

3.Leveling tool or method.

Make Opening (If Mounting in Drop Ceiling)

IMPORTANT

Be sure to choose an accessible position for the air cleaner. Check that the area directly below the posi- tion of the air cleaner is open and free and clear of obstructions.

See Fig. 4 and use these instructions to mount the F118 as part of a drop ceiling:

1.Remove the tile(s) from the drop ceiling to open a space of approximately 24 x 48 in. (610 x 1220 mm). The area between the drop ceiling and the structural ceiling must be at least 12 in. (345 mm) and clear of ducts, pipes, and other obstacles.

2.Size and frame the opening to fit the air cleaner cabinet as closely as possible. The cabinet must fit snugly in the opening; allow no more than 1/4 in. (6 mm) from the opening to each side of the cabinet.

3.Cover the framing and any unused portion of the open- ing with wallboard, plywood, or other material. Finish to match the ceiling.

68-0209-2 Revised 11-07

4

Page 4
Image 4
Honeywell F118 Installation, When Installing This Product, Unpack Air Cleaner, Make Opening If Mounting in Drop Ceiling