F118
1
1
SUSPENDED CEILING
STRUCTURAL CEILING |
|
PLACE WIRE SUPPORTS AS CLOSE AS POSSIBLE |
|
TO F118 SUPPORT SHOULDER POSITIONS, |
|
APPROXIMATELY 5 IN. (127 MM) FROM ENDS. | 1 |
| |
2 |
|
F118
1
DROP
CEILING
24 IN. | 24 IN. |
(610 MM) | (610 MM) |
24 IN.
(610 MM)
REMOVE
(1219 X 610 MM) SPACE.
SUPPORT SHOULDER
LOCATIONS (8)
BEND TABS TO
HOLD MOUNT
ON AIR CLEANER
SUPPORT SHOULDER (1 OF 8)
SUPPORT SHOULDER
POSITIONS
1BE SURE TO TWIST THE SUPPORT WIRE A MIINIMUM OF FOUR TIMES TO PROPERLY BEAR WEIGHT.
2THERE MUST BE 12 IN. (305 MM) BETWEEN DROP
CEILING AND STRUCTURAL CEILING.
REINFORCED
M16212A
Fig. 4. Mounting procedure.
Mount Air Cleaner Cabinet
WARNING
Fire or Electric Shock Hazard.
Can cause personal injury or equipment damage. Do not connect the power source until after electronic air cleaner is mounted.
1.The cabinet has multiple slots. See Fig. 4. Insert the support shoulders into the selected slots.
2.Bend the two tabs on each support shoulder until the tabs are flush with the cabinet.
3.Thread wire through the support shoulders. Make sure the wire is strong enough to support the total weight of the air cleaner. Never rest the air cleaner on the
4.Twist the support wire a minimum of four times.
WARNING
Equipment Falling Hazard.
Can cause personal injury, structural weakening, buckling, or damage to equipment.
Be sure platform is stable and can support combined weight of installer and equipment.
Use assistant to help support equipment during instal- lation.
5 |