Wiring ANN-RLY Module to FACP Setting DIP Switches
Refer to Table 2 and Figure 3 for wiring connections.
FACP | ||
Terminal 4 | ||
Terminal 3 | (+) | (+) |
Terminal 2 | (A) | A |
Terminal 1 | (B) | B |
Table 2: Wiring
Each
A maximum of 8 devices can be connected to the FACP
C
NC
NO
C
NC
NO
Figure 3: Wiring
Notes:
1.All connections/sources are to be
2.12 - 18 AWG (0.75 - 3.25 mm2) wire for 24 VDC circuit is acceptable. Refer to the appropriate FACP manual.
3.Power wire distance limitation is set by 1.2 volt maximum line drop from source to end of circuit.
4.Maximum distance from FACP to last ANN- BUS device must not exceed 1,250 feet
(380 m). Refer to Wiring Distance Table in appropriate FACP manual for wire gauge and distance limitations.
5.Common, Normally Closed and Normally Open terminals for each relay follow the same pattern as illustrated above.
ID Number | DIP Switch SW1 | |||||||||||
(Address) |
|
|
|
|
|
|
|
|
|
|
|
|
(not valid) 00 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
01
02
03
04
05
06
07
08
One
Northford, CT 06472
USA TEL: (203)
www.firelite.com
© 2006
3 |