Honeywell HA40 technical manual Specifications

Models: HA40

1 39
Download 39 pages 49.91 Kb
Page 36
Image 36

HA40 4-Channel Controller

5 Specifications

 

 

 

 

 

 

Certifications:

CSA C22.2 No. 1010-1, ISA S82.02

 

 

 

 

CSA C22.2 No 152 (for combustibles using mA

Input power:

100-240 VAC, 50/60 Hz

input)

 

24 VDC

UL 1604/C22.2 No. 213 (NEMA 4X = Div 2, Gr A,

 

 

 

 

B, C, D; NEMA 7 = Div 1, Gr , B, C, D

DC output power:

15 watts (internal supply)

EN55011 & EN61000 (CE mark))

 

50 watts (optional external supply)

 

 

 

 

 

 

 

 

 

 

 

 

Relay output rating:

5A, 28 VDC or 250 VAC (resistive load)

 

 

 

 

 

 

Optional relay output rating

5A, 28 VDC or 250 VAC (resistive load)

 

 

 

 

 

 

Optional milliamp loop

10 bit 4-20mA output. Maximum load 750 ohms

 

output

with nominal 24 Vdc

 

 

 

 

 

 

Communication:

RS232 Modbus

 

 

 

 

 

 

Length of communication

 

 

 

 

lines:

 

 

 

 

 

 

 

 

 

Operating environment:

Industrial

 

 

 

 

 

 

Operating temperature

-25 to 50ºC (-13ºF to 122ºF)

 

range:

 

 

 

 

 

 

 

 

 

Operating humidity range:

0 to 90% RH non-condensing

 

 

 

 

 

 

Operating altitude:

2000m (6562 ft)

 

 

 

 

 

 

Audible alarm:

100 dB

 

 

 

 

 

 

Display:

128 x 64, backlight graphic LCD

 

 

 

 

 

 

Visual Indicators:

6 LED status indicators

 

 

 

 

 

 

Pollution degree:

N4: 3

 

 

 

 

 

 

Enclosure (N4):

NEMA 4X, Div. 2, Groups A,B,C,D, Category II

 

 

 

 

 

 

Enclosure (XP):

NEMA 7, Div. 1 & 2, Groups B,C,D

 

 

 

 

 

 

Dimensions (H x W x D):

N4: 10.32” x 8.92” x 3.17” (23.62 x 22.66 x 8.05cm)

 

 

XP: 15.10” x 13” x 6.25” (36.2 x 33 x 15.88cm)

 

 

 

 

 

 

Weight:

N4: 2.27 Kg XP: 18.14 Kg

 

 

 

 

 

 

HA40 Technical Manual

6-2

Revision 1 (07/08)

Page 36
Image 36
Honeywell HA40 technical manual Specifications