AUXILIARY SWITCH RATINGS (amperes): M94XXE has 1 spdt switch.

M94XXF has 2 spdt switches.

ONE CONTACT a

120v

240v

Full Load

7.2

3.6

Locked Rotor

43.2

21.6

a4O VA pilot duty, 1201240 Vat on opposite contact.

DIMENSIONS: See Fig. 1.

UNDERWRITERS LABORATORIES INC. LISTED

File No. E4436; Guide No. XAPX.

CANADIAN STANDARDS ASSOCIATION CERTIFIED:

General Listing File No. LR1620,400-E-)

‘U

STROKE STROKE RUNNING BREAKAWtY

15 set

30 set

75

18.51

150

[17.0]

 

 

 

 

 

 

30 set

1 min

150

[17.0]

300

[34.0]

1.2 min 1 2,4 minD 1 300 134.01 1 600 168.01

aBreakaway torque is the maximum torque available to overcome occasional large loads such as a seized damper or valve. MOTOR MUST NOT BE USED CONTINUOUSLY AT THIS RATING.

bStalling of 2,4 min motor will damage motor.

ACCESSORIES:

ES6501 17 Explosion-proof Housing-Encloses motor for use in explosive atmospheres. Not for use with Q601, Q618, and Q455 Linkages. Order from Nel- son Electric Co. Requires Honeywell 7617DM Cou- pling.

Q607 External Auxiliary Switch-Controls auxiliary equipment as a function of motor position.

Q605 Damper Linkage-Connects motor to damper.

INCLUDES MOTOR CRANK ARM.

0618 Linkage-Connects Modutrol motor to water or steam valve.

Q601 Bracket and Linkage Assembly-Connects Modutrol motor to water or steam valve.

Ql OOA,B Linkage-Connects Modutrol motor to but-

WHEN INSTALLING THIS PRODUCT...

1.Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.

2.Checkthe ratings given in the instructions andon the product to make sure the product is suitable for your application.

3.Installer must be a trained, experienced service technician.

4.After installation is complete, check out product operation as provided in these instructions.

terfly valve. Requires adapter bracket packed with motor.

Q209E,F Potentiometer-Limits minimum position of motor.

Q68 Dual Control Potentiometer-Controls 1 through 9 additional motors.

Q181 Auxiliary Potentiometer-Controls 1 or 2 addi- tional motors.

221455A Motor Crank Arm-Infinitely adjustable crank arm. Approximately 0.75 inches shorter than the 4074ELY crank arm, can rotate through downward position and clear base of motor without requiring use of adapter bracket.

220741A Screw Terminal Adapter-converts the stan- dard quick-connect terminals to screws terminals.

Transformers-mounted internally, provide 24 Vat power to motor

198162JA-24 Vat; 50/60 Hz (for electrical iso- lation).

198162EA-120 Vat; 50160 Hz.

198162GA-220 Vat; 50160 Hz. 198162Al-120/208/240 Vat; 50160 Hz.

Q7130A-Interface Module with selectable voltage ranges (4-7 Vdc, 6-9 Vdc, and 10.5-13.5 Vdc). Adapts motor to M71 XX function.

Q7230A-Interface Module, selectable voltage or cur- rent control, with adjustable null and span. Adapts motor to M72XX function; 4 to 20 mA or 2 to 10 Vdc.

Q7330A-Interface Module, for W936 economizer ap- plications. Adapts motor to M73XX function.

Q7630A-Interface Module, 3-wire 14-17 Vdc control with minimum position capability. Adapts motor to M76XX function.

4074BYK-Control up to 6 M9lXX motors in unison from one Series 90 controller.

4074EAU-Drive 2 or 3 M91 XX motors from a W973 Single-zone Logic Panel or W7100 Discharge Air Controller.

4074EDC-Drive one M91XX motor from a 4-20 mA Controller.

4074EED-Drive up to 4 M91 XX motors from a 4-20 mA Controller.

221508A Resistor Board-Plugs onto quick-connects in wiring box of M9lXX motor. Can be used in place of 4074BYK, EAU, EDC, or EED resistor kits (func- tions described above).

7616ADW Motor Crank Arm-Approximately 0.75 inches shorter than the 7616BR crank arm, can rotate through the downward position and clear base of motor without requiring use of adapter bracket.

1.Disconnect power supply before beginning in- stallation to prevent eiectrical shock and equip- ment damage.

2.Never turn the motor shaft by hand or with a wrench-this will damage the motor.

3.Always conduct a thorough checkout when in- stallation is complete.

1

363-2195-l

Page 3
Image 3
Honeywell M9491, M9494, M9481 Underwriters Laboratories INC. Listed, Canadian Standards Association Certified, Accessories