Dimensions

10Installation Guide PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2

Dimensions

 

ENC1

ENC2

Height:

13.9" [0.353 m]

13.9" [0.353 m]

Width:

17" [0.4318 m]

18.9" [0.48006 m]

Depth:

9" [0.2286 m]

9" [0.2286 m]

Metal thickness: .05" [1.27 mm]

Color: Autumn White

Installation holes: Four hangers in a rectangular pattern 12.1” [0.30734 m] H x 16" [0.40640 m] W

Conduit Knockouts

 

½" [0.0127 m]

2" [0.05080 m]

Back:

9

2

Top:

9

2

Right Side:

2

1

Left Side:

2

1

Power Supply

Use PRO22E1PS or other approved power supply. (See Installation Manual for details).

Maintenance

Oil lock once per year. If battery backup is used, change battery every 2 to 2 1/2 years.

Installation Instructions

1.Measure and install four mounting screws with heads smaller than .4" [0.01016 m] using proper techniques for the material on which the PRO-2200 is being mounted. Use a rectangular screw pattern 12.1" [0.30734 m] H x 16" [0.40640 m] W. Leave the screws exposed approximately 1/2" [0.0127 m].

2.Open the door of the enclosure and place the hanging slots over the mounting screws. Push the enclosure over the mounting screws and allow the screws to slide into the slots. Finish tightening the mounting screws to securely hold the enclosure.

3.Run all appropriate wiring to the case. Mark each wire as to the panel, location and input type. All cable shields should tie to the copper grounding lug found on the bottom right of the enclosure.

4.Install the required panels into the metal runners. The PRO22E1PS should be placed in the right most location and installed according to its own instruction manual. The PRO22IC should be installed next to it as the right-most panel.

5.Wire the readers, input and output connections (see wiring guide at end of manual)

6.CHECK ALL CONNECTIONS PRIOR TO POWERING UP THE ENCLOSURE AND PANELS.

Page 9
Image 9
Honeywell PRO22ENC2, PRO22ENC1 Dimensions, Conduit Knockouts, Power Supply, Maintenance, Installation Instructions