A.4 | Setting Range Values (Local Zero and Span), Continued | |||||||||
|
|
|
|
|
|
|
|
|
| |
Procedure, continued |
|
|
|
|
|
|
| |||
| Table |
|
| Setting Range Values Using Local Zero and Span | ||||||
|
|
|
|
|
| Adjustments, Continued |
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Step |
|
|
| Action |
| ||
|
|
|
|
|
|
|
| |||
|
| 4 | Turn ON transmitter power and let it warm up for a few minutes. |
| ||||||
|
|
|
| Using an accurate pressure source, apply desired zero equivalent |
| |||||
|
|
|
| pressure to transmitter. |
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ATTENTION | For differential pressure transmitters, apply pressure |
| |||
|
|
|
| to the high pressure head for positive range values or vent both |
| |||||
|
|
|
| heads to atmosphere for zero. If zero is to equal a negative value, |
| |||||
|
|
|
| apply the equivalent pressure to the low pressure head. For |
| |||||
|
|
|
| example, if zero is to equal |
| |||||
|
|
|
| the low pressure head and vent the high pressure head for the zero |
| |||||
|
|
|
| adjustment. |
|
|
|
| ||
|
|
|
|
| ||||||
|
| 5 | Check that milliammeter reading is 4 mA. |
| ||||||
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| If reading … | Then… |
|
| |
|
|
|
|
|
| is less or greater than 4 mA | go to Step 6. |
|
| |
|
|
|
|
|
| is correct |
| go to Step 7. |
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
| ATTENTION | If you have the smart meter with local zero and |
| |||
|
|
|
| span adjustment option, you may substitute the smart meter |
| |||||
|
|
|
| readings for the milliammeter readings. For example, with zero input |
| |||||
|
|
|
| pressure applied assume that the meter reads 4 inH2O instead of 0 |
| |||||
|
|
|
| inH2O. In this case, the meter reading is greater than 0 (or 4 mA). |
| |||||
|
| 6 | a. Press and hold ZERO button on local zero and span assembly or |
| ||||||
|
|
|
|
| smart meter. |
|
|
|
| |
|
|
|
|
|
|
|
| |||
|
|
|
|
| ATTENTION | The smart meter readings revert to the default unit of |
| |||
|
|
|
| percent (%) during this operation. If the error code Er0 appears on |
| |||||
|
|
|
| the display, you are working with a model STD110 transmitter that |
| |||||
|
|
|
| does not support the local zero and span adjustments. |
| |||||
|
|
|
| b. Press Decrease button once to complete this function. |
| |||||
|
|
|
|
|
|
|
| |||
|
|
|
|
| ATTENTION | The smart meter display goes blank for a 1/2 |
| |||
|
|
|
| second and then returns reading 0%. |
| |||||
|
|
|
| c. Check that milliammeter reading equals 4 mA and release ZERO |
| |||||
|
|
|
|
| button. |
|
|
|
| |
|
|
|
|
|
|
|
| |||
|
|
|
|
| ATTENTION | If milliammeter reading doesn’t change, be sure you |
| |||
|
|
|
| are not working with a model STD110 transmitter that ignores local |
| |||||
|
|
|
| adjustments. The smart meter readings return to the set engineering |
| |||||
|
|
|
| units after you release the ZERO button. |
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| Continued on next page | ||