A.4

Setting Range Values (Local Zero and Span), Continued

 

 

 

 

 

 

 

 

 

 

 

 

Procedure, continued

 

 

 

 

 

 

 

 

 

 

Table A-3

 

 

 

Setting Range Values Using Local Zero and Span

 

 

 

 

 

 

 

Adjustments, Continued

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Step

 

 

 

 

 

Action

 

 

 

 

 

 

 

 

 

 

 

7

Using an accurate pressure source, apply pressure equivalent to

 

 

 

 

 

desired upper range value to transmitter.

 

 

 

 

 

 

ATTENTION

For differential pressure transmitters, apply pressure

 

 

 

 

 

to the high pressure head and be sure that the pressure to the low

 

 

 

 

 

pressure head is at its reference value.

 

 

 

 

 

 

 

 

8

Check that milliammeter reading is 20 mA.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If reading …

 

Then…

 

 

 

 

 

 

 

 

 

is not exactly 20 mA

 

go to Step 9.

 

 

 

 

 

 

 

 

 

is correct

 

 

go to Step 10.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ATTENTION

If you have the smart meter with local zero and

 

 

 

 

 

span adjustment option, you may substitute the smart meter readings

 

 

 

 

 

for the milliammeter readings. For example, with URV input pressure

 

 

 

 

 

applied assume that the meter reads 396 inH2O instead of 400

 

 

 

 

 

inH2O. In this case, the meter reading is less than 100% (or 20 mA).

 

 

 

 

 

 

 

 

9

a. Press and hold SPAN button on local zero and span assembly or

 

 

 

 

 

 

 

smart meter.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ATTENTION

The smart meter readings revert to the default unit of

 

 

 

 

 

percent (%) during this operation. If the error code Er0 appears on

 

 

 

 

 

the display, you are working with a model STD110 transmitter that

 

 

 

 

 

does not support the local zero and span adjustments. If the error

 

 

 

 

 

code Er4 appears, you are trying to set a SPAN value that is outside

 

 

 

 

 

acceptable limits for your transmitter. Readjust applied pressure to

 

 

 

 

 

be within acceptable range limits and repeat this procedure.

 

 

 

 

 

b.

 

Press Increase ￿ button once to complete this function.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ATTENTION

The smart meter display goes blank for a 1/2

 

 

 

 

 

second and then returns reading 100%.

 

 

 

 

 

c. Check that milliammeter reading equals 20 mA and release SPAN

 

 

 

 

 

 

 

button.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ATTENTION

If milliammeter reading doesn’t change, be sure you

 

 

 

 

 

are not working with a model STD110 transmitter that ignores local

 

 

 

 

 

adjustments. The smart meter readings return to the set engineering

 

 

 

 

 

units after you release the SPAN button.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Continued on next page

2/05

ST 3000 Release 300 Installation Guide

57