B.1 North American Classification of Hazardous Locations, Continued

Entity Concept

 

 

Under entity requirements, the concept allows interconnection of

 

 

 

intrinsically safe apparatus to associated apparatus, not specifically

 

 

 

examined in such combination. The criteria for interconnection is that the

 

 

 

voltage (Vmax ) and current (Imax ), which intrinsically safe apparatus

 

 

 

can receive and remain intrinsically safe, considering faults, must be

 

 

 

equal to or greater than the voltage (Voc or Vt ) and current (Isc or It )

 

 

 

levels which can be delivered by the associated apparatus, considering

 

 

 

faults and applicable factors. In addition, the maximum unprotected

 

 

 

capacitance (Ci ) and inductance (Li ) of the intrinsically safe apparatus,

 

 

 

including interconnecting wiring, must be less than or equal to the

 

 

 

capacitance (Ca ) and inductance (La ) which can be safely connected to

 

 

 

the associated apparatus. If these criteria are met, then the combination

 

 

 

may be connected and remain intrinsically safe. Both FMRC and CSA d

 

 

 

entity parameters are defined in Table B-1 and B-2.

 

Table B-1

Factory Mutual (FM) Approval

 

 

 

 

 

 

 

 

 

 

Code

 

Description

 

 

 

 

1C

 

Explosionproof for Class I, Division 1, Groups A, B, C & D.

 

 

 

 

 

 

Dust-Ignitionproof for Class II, Division 1, Groups E, F & G.

 

 

 

 

 

 

Suitable for Class III, Division 1. Conduit seals required within

 

 

 

 

 

 

18” of enclosure, Group A only.

 

 

 

 

 

 

Intrinsically Safe for use in Class I, Division 1, Groups A, B, C

 

 

 

 

 

 

& D; Class II, Division 1, Groups E, F & G; Class III, Division 1,

 

 

 

 

 

 

T4 at 40°C, T3A at 93°C maximum ambient, when connected

 

 

 

 

 

 

in accordance with Honeywell drawing 51204241.

 

 

 

 

 

 

Nonincendive for use in Class I, Division 2, Groups A, B, C &

 

 

 

 

 

 

D; Suitable for Classes II & III, Division 2, Groups F & G, T4 at

 

 

 

 

 

 

93°C maximum ambient, hazardous locations. 42 Vdc max.

 

 

 

 

 

 

Environmental: Indoor and outdoor hazardous locations

 

 

 

 

 

 

(NEMA 4X).

 

 

 

 

 

 

 

 

 

 

 

 

Continued on next page

2/05

ST 3000 Release 300 Installation Guide

87