B.1 North American Classification of Hazardous Locations, Continued

Table B-1

Factory Mutual (FM) Approval, Continued

 

Intrinsic Safety

Class I, II, III, Divisions 1 and 2,

Entity Parameters (1)

Groups A - G

 

VMax

42.4 V

 

 

 

 

 

 

IMax =

225 mA

 

 

 

 

 

 

PMax =

1.2 W

 

 

 

 

 

 

Ci =

4.2 nF

 

 

Li =

0

With no integral indicator, or with

 

 

 

integral Smart Meter, option SM.

 

 

 

 

 

Li =

150 H

With Analog Meter, option ME.

(1)Install in accordance with Honeywell drawing 51204241.

Table B-2

Canadian Standards Association (CSA)

 

 

 

 

 

 

Code

 

 

Description

 

 

 

 

 

 

2j

 

Explosion Proof for Class I, Division 1, Groups B, C & D.

 

 

 

Dust-Ignition-Proof for Class II, Division 1, Groups E, F & G;

 

 

 

Class III, Division 1. Conduit seals not required. 42 Vdc max.

 

 

 

Intrinsically Safe for Class I, Groups A, B, C & D; Class II,

 

 

 

Groups E, F & G; Class III, Divisions 1, T4 at 40°C, T3A at

 

 

 

93°C maximum ambient. Install per Honeywell drawing

 

 

 

51204242.

 

 

 

 

Suitable for Class I, II & III, Division 2, Groups A, B, C, D, E, F

 

 

 

& G hazardous locations, T4 at 93°C. 42 Vdc max.

 

 

 

Environmental: Indoor and outdoor hazardous locations

 

 

 

(Encl 4X).

 

 

 

 

 

 

 

 

 

CSA Certified Barriers (1)

Class I, II, III, Division 1 and 2,

 

 

 

 

Groups

 

 

28V / 200

A - G

 

 

 

 

 

 

20V / 150

C - G

 

 

 

 

 

(1)Install in accordance with Honeywell drawing 51204242.

88

ST 3000 Release 300 Installation Guide

2/05