BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS
17 63-4523—02
Economizer
Changeover Setpoint AV 77 Present_Value (R,W) √√
Economizer Minimum
Position AV 78 Present_Value (R,W) √√
Mechanical Cooling
Enabled BV 79 Present_Value (R,W) √√
Mixed Air Setpoint AV 80 Present_Value (R,W) √√
Heatpump Model
Configuration Options GRP 81 Pr esent_Value (R) √ √
High Balance Point AV 82 Present_Value (R,W) √√
Low Balance Point AV 83 Present_Value (R,W) √√
Comfort Mode BV 84 Present_Value (R,W) √√
Reversing Valve
Configuration BV 85 Present_Value (R,W) √√
Compressor Interlock BV 86 Present_Value (R,W) √√
Dehumidification Model
Configuration Options GRP 87 Pr esent_Value (R) √ √
RH Display BV 88 Present_Value (R,W) √√
Dehumidification RH
Setpoint AV 89 Present_Value (R,W) √√
Dehumidification
Hysterisys AV 90 Present_Value (R,W) √√
Dehumidification Low
OA Lockout AV 91 Present_Value (R,W) √√
Dehumidification
Lockout Functions BV 92 Present_Value (R,W) √√
Dehumidification Output
Status BI 93 Present_Value (R) √√
Humidification Model
Configuration Options GRP 94 Pr esent_Value (R) √ √
Humidification RH
Setpoint AV 95 Present_Value (R,W) √√
Eff (Effective) Reset
Humidification RH Spt
(Setpoint)
AV 96 Present_Value (R) √√
Humidification High
Limit Spt (Setpoint) AV 97 Present_Value (R,W) √√
Low RH Setpoint AV 98 Present_Value (R,W) √√
Low Temp Reset RH
Setpoint AV 99 Present_Value (R,W) √√
High Temp Reset RH
Setpoint AV 100 Present_Value (R,W) √√
Humidifier Output AV 101 Present_Value (R) √√
Local Schedule SCH 102 Present_Value (R,W) √√√√√