BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS
63-4523—02 8
INTEGRATION

This section provides compatibility and programming information useful when setting up TB7600 Series thermostats on a WEBs-

AX building automation system.

Global Commands

The following figure shows which objects from the thermostat can be monitored and commanded from the BAS front-end.

Fig. 6. Global commands from a BAS front-end to a TB7600 series thermostat.

GLOBAL COMMAND CONTROL LEVEL DEVICE LEVEL
BAS FRONT-END TB7600 SERIES TSTAT
MSTP NETWORK
GLOBAL COMMANDS ALL DEVICES
(ALL THERMOSTATS)
OUTDOOR TEMPERATURE
OUTDOOR TEMPERATURE AND HVAC PLANT CURRENT MODE
BAS CURRENT ENERGY SAVINGS MODE
GLOBAL COMMANDS SPECIFIC DEVICES
(SPECIFIC AREA THERMOSTATS)
SCHEDULE
SCHEDULE AND OUTDOOR TEMPERATURE
RESTRICT SER ACCESS TO THERMOSTAT
ROOM TEMPERATURE FOR TESTING AND OVERRIDE
OUTDOOR TEMPERATURE (AV9)
SYSTEM MODE (MV13)
FAN MODE (MV15)
OCCUPANCY COMMAND (MV12)
OCCUPIED HEATING SETPOINT (AV42)
UNOCCUPIED HEATING SETPOINT (AV44)
OCCUPIED COOLING SETPOINT (AV43)
UNOCCUPIED COOLING SETPOINT (AV45)
KEYPAD LOCKOUT (MV18)
ROOM TEMPERATURE (AV7)
M32570