BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS
63-4523—02 18
Standard Object Types SupportedTable 6. Standard Object Types Supported
a The following AV’s are defined as read only. When Out_of_Service properties is set to true, the Present_Value if written is not
derived from the application level of the thermostat.
• Room Humidity (AV11)
• PI Heating Demand (AV20)
• PI Cooling Demand (AV21)
• Economizer Output (AV22)
• Eff Reset Humidification RH Spt (AV96)
• Humidifier Output (AV101)
b Object_Name property is writable for 1 object only :
• Room_Temperature (AV7)
Proprietary PropertiesTable 7. Proprietary Properties
Object Type Supported
Objects Dynamically
Creatable Dynamically
Deletable
Optional
Properties
Supported Writable Properties
Analog Input ; Reliability Out_of_Service
Analog Value ; Reliability
Present_Valuea
Out_of_Servicea
Object_Nameb
Binary Input ;
Reliability
Active_Text
Inactive_Text
Out_of_Service
Binary Value ;
Reliability
Active_Text
Inactive_Text
Present_Value
Out_of_Service
Device ;
Max_Master
Max_Info_frames
Object_Identifier
Object_name
Max_Master
Group ; N/A N/A
Multi-state Value ; Reliability
States_Text
Present_Value
Out_of_Service
Schedule ; Weekly_schedule Present_Value
Weekly_Schedule
Property name ID BACnet Data type Description
Major_Version 1000 CharacterString
The version number of the BACnet communications
module. This is the hardware version number.
MS/TP_Address 1001 Unsigned Display the MAC layer address of the module
MS/TP_Baud_Rate 1002 Unsigned Display the communication baud rate of the module
Sensor_Offset 1005 REAL
Display the temperature or humidity calibration value.
The range is –5.0 deg F to 5.0 deg F for a temperature
and –15% to 15% for humidity.