W8600F AIR CLEANER MONITOR
12.Connect the three wires from the W8600F to the EAC terminals 1, 3 and 4.
NOTE: Connect terminal 1 to 1, 3 to 3 and 4 to 4.
13.Turn on the EAC power.
14.Turn on the system fan.
15.Push the W8600F reset button. All four indicators on the display will flash five times. The On indicator will stay active as long as the EAC and the system fan are on.
SYSTEM CHECKOUT
Checkout (With EAC Running)
1.Be sure the battery is installed in the W8600F.
2.Press the reset button on bottom of the W8600F. All four indicatiors on the display will flash five times and then ON and FAULT will remain indi- cated.
3.Connect terminal 3 to terminal 4 and the function panel indicates ON. FAULT will turn off.
4.Disconnect terminal 3 from terminal 4. The W8600F is functional.
Checkout (Without EAC)
1.Be sure the battery is installed in the W8600F.
2.Press the reset button on the bottom of the W8600F. All four indicators on the display will flash five times, then ON and FAULT will remain indi- cated.
3.Connect 9 Vdc to terminal 4 with terminal 1 as ground (use a
4.Connect terminal 3 to terminal 4 and the function panel indicates ON, FAULT will turn off.
5.Remove 9 Vdc input. The W8600 is functional.
TROUBLESHOOTING
Refer to Table 3.
Table 3. W8600F Troubleshooting Information.
|
|
|
|
|
|
Display |
| Condition | Solution |
| |
|
|
|
|
| |
Blank |
| EAC is not operating. | Turn on EAC. Function panel indicates ON. |
| |
|
|
|
|
| |
|
|
| Press W8600F reset button. DISPLAY flashes five |
| |
|
|
| times. |
| |
|
|
|
|
| |
|
| ON indicator does not flash when | Check W8600F battery for 2.7 volts. Replace with |
| |
|
| reset button is pressed. | BR2032 lithium battery if necessary. |
| |
|
|
|
|
| |
All four indicators flash |
| Power supply does not have an | Assemble jumper on pins 1 and 2 of J3 connector on |
| |
after pressing reset button, | airflow switch. | power supply. |
| ||
but ON is not displayed |
|
|
|
|
|
with EAC operation. |
| Voltage between W8600F | Replace W8600F. |
| |
|
| terminals 1 (ground) and 4 (+10 to |
|
|
|
|
| +15 Vdc). |
|
|
|
|
|
|
|
| |
|
| No voltage, low voltage or wrong | Check wiring between W8600F and EAC. Correct |
| |
|
| polarity. | wiring, if necessary. |
| |
|
|
|
|
| |
|
| No voltage between EAC terminals | Check the driver board and cable installation. Correct |
| |
|
| 1 (ground) and 4 (+10 to +15 Vdc). | installation if necessary. |
| |
|
|
|
|
| |
BATTERY, SERVICE or |
| Incorrectly wired. | Check wiring between W8600F and EAC. Correct |
| |
FAULT, but not ON |
|
| wiring, if necessary. |
| |
|
|
|
|
| |
ON and BATTERY |
| Bad battery. | Check W8600F battery for 2.7 volts. Replace with |
| |
|
|
| BR2032 lithium battery, if necessary. |
| |
|
|
|
|
| |
ON and SERVICE |
| EAC cells and prefilters are dirty. | Wash and reinstall the EAC cells and prefilters. Press |
| |
|
|
| the W8600F reset button. ON flashes five times and |
| |
|
|
| SERVICE is off. |
| |
|
|
|
|
| |
ON and FAULT |
| Damaged cells. | Repair or replace cells. |
| |
|
|
|
|
| |
|
| Power supply problem. | Press EAC test button and verify output voltage. |
| |
|
|
| Replace power supply, if necessary. |
| |
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|