Mounting/Dismounting Modules Excel 800
EN1B-0410GE51 R0908A 18

Connecting Laptops (XL-Online/CARE)

Connect a laptop (on which e.g., XL-Online or CARE has
been installed) to the HMI interface or LONWORKS interface
of the XCL8010AU Controller Module by means of
– the XW885 cable or
– the XW585 cable connected with an XW586 Cable.

XCL8010AU Terminals

74
14 10 7
2
3
4
78
73
13 9 6
1
77
72
12 8 5
76
71
11
75
24
V~
24
V~
24
V~
24
V~0
LON
2
C- C-
C+ C+
LON
2
LON
1
LON
1
24
V~0
24
V~0
NC
24
V~0
COM
BCOM
B
COM
ACOM
A
SHIELD SHIELD
87654321

*

*Watch Dog
Relay
Fig. 26. Terminal assignment and internal connections of
the XCL8010AU Controller Module
Table 12. Description of XCL8010AU terminals
ter-
minal signal comment
71, 75 COM a 2-wire communication bus
(LON/Panel Bus)
72, 76 COM b 2-wire communication bus
(LON/Panel Bus)
73, 77 24 V~ Power supply for I/O modules
74, 78 24 V~0 Power supply for I/O modules
1 24 V~ Power supply f rom transformer
2 24 V~0 Power supply from transformer
3 24 V~0 Alarm/watchdog output
4 NC Alarm/watchdog output
5, 8 C+ C-Bus
6, 9 C- C-Bus
7, 10 Shield C-Bus shield
11, 12 LON LONWORKS IN
13, 14 LON LONWORKS OUT
Features

LONWORKS Interface and Terminals

The XCL8010AU Controller Module features
An RJ45 socket serving as an interface
to connect laptops or HMIs to the LONWORKS Bus
LONWORKS terminals 11, 12, 13, and 14
to connect LONWORKS Bus I/O modules or other
LONWORKS devices to the XCL8010AU Controller or other
LONWORKS controllers.
Fig. 27. LONWORKS interface and LONWORKS terminals
LONWORKS Interface Signals on RJ45 Socket
Table 13. Signals of LONWORKS interface
pin signal type
1 Connection to LONWORKS Bus
2 Connection to LONWORKS Bus
3 8 Not used

LONWORKS Service LED and Button

The XCL8010AU Controller Module is equipped with a
LONWORKS service button and corresponding LONWORKS
Service LED (status: yellow/OFF).
1
LON
2
Fig. 28. LONWORKS service button (1) and service LED (2)
See also section "Troubleshooting" on page 31.