Hoshizaki DCM-750BAH(-OS), DCM-750BWH(-OS) DCM-750BWH-OS, Connection to a Closed Loop System, Fig

Models: DCM-750BAH(-OS) DCM-750BWH(-OS)

1 32
Download 32 pages 13.26 Kb
Page 21
Image 21
b) Connection to a Closed Loop System

b) Connection to a Closed Loop System

Condenser water supply inlet is 1/2" female pipe thread (FPT). A minimum of 3/8" OD copper tubing is recommended for the condenser water supply line.

Condenser return outlet is 3/8" FPT. A minimum of 3/8" OD hard pipe is recommended for the condenser return line.

Shut-off valves and drain valves should be installed at both the condenser water supply inlet and condenser return outlet.

The water supply to the condenser should not drop below 4 GPM.

The pressure differential between the condenser water supply inlet and condenser return outlet must be no less than 10 PSIG.

When using a glycol blend, the solution mixture should be less than 30% glycol.

In order to maintain the proper high side pressure, the condenser water supply inlet temperature should not drop below 45°F (7°C) and the condenser return outlet temperature must be in the 104°F to 115°F (40°C to 46°C) range. Once the icemaker installation is complete, confirm the condenser return outlet temperature 5 minutes after a freeze cycle starts. If the outlet temperature is not in the proper range, adjust the water‑regulating valve to bring it into range.

Storage Bin

Drain Outlet

3/4" FPT

Drip Tray

Drain Outlet

3/4" FPT

Icemaker

Stand

Vent

Tube

Icemaker Water

 

Supply Inlet

Icemaker Water Supply

1/2" FPT

 

Line Shut-Off Valve

Condenser

Icemaker Water Supply

Return Outlet

3/8" FPT

Line Drain Valve

 

Condenser Return

 

Line Shut-Off Valve

 

Condenser Water Supply

 

Line Shut-Off Valve

 

Condenser Return

 

Line Drain Valve

DCM-750BWH(-OS)Connection to a Closed Loop SystemManual backgroundManual backgroundManual backgroundCondenser Water Supply Condenser Water Line Drain Valve Supply Inlet

1/2" FPT

Separate piping to approved drain. Leave a two-inch (5 cm) vertical air gap between the end of each pipe and the drain.

Two-inch (5 cm) air gap

Fig. 6

DCM-750BWH(-OS)

Floor Drain

 

Connection to a Closed Loop System

21

Page 21
Image 21
Hoshizaki DCM-750BAH(-OS), DCM-750BWH(-OS) instruction manual DCM-750BWH-OS, b Connection to a Closed Loop System, Fig