Nominal Input |
|
|
|
|
|
|
|
Current (A rms) | 9.7 | 9.0 | 7.0 | 6.8 | 6.4 | 9.1 | 5.9 |
|
|
|
|
|
|
|
|
Maximum Rated |
|
|
|
|
|
|
|
Input Wattage |
|
|
|
|
|
|
|
Rating (Watts) | 930 | 1034 | 1348 | 1348 | 1348 | 1348 | 1348 |
|
|
|
|
|
|
|
|
Maximum Rated |
|
|
|
|
|
|
|
VA | 970 | 1079 | 1406 | 1406 | 1406 | 1406 | 1406 |
|
|
|
|
|
|
|
|
Efficiency (%) of |
|
|
|
|
|
|
|
Maximum Rated |
|
|
|
|
|
|
|
Output Wattage | 86 | 87 | 89 | 89 | 89 | 89 | 89 |
|
|
|
|
|
|
|
|
Power Factor | 0.97 | 0.97 | 0.97 | 0.97 | 0.97 | 0.97 | 0.97 |
|
|
|
|
|
|
|
|
Leakage Current |
|
|
|
|
|
|
|
(mA) | 0.42 | 0.50 | 0.83 | 0.87 | 0.92 | 0.96 | 1.00 |
|
|
|
|
|
|
|
|
Maximum Inrush |
|
|
|
|
|
|
|
Current (A peak) | 30 | 30 | 30 | 30 | 30 | 30 | 30 |
|
|
|
|
|
|
|
|
Maximum Inrush |
|
|
|
|
|
|
|
Current duration |
|
|
|
|
|
|
|
(mS) | 20 | 20 | 20 | 20 | 20 | 20 | 20 |
|
|
|
|
|
|
|
|
Maximum British |
|
|
|
|
|
|
|
Thermal Unit |
|
|
|
|
|
|
|
Rating | 3174 | 3530 | 4600 | 4600 | 4600 | 4600 | 4600 |
|
|
|
|
|
|
|
|
Replacing the fans and power supplies
If a cooling fan or power supply fails, you must replace it. Replacement usually takes no longer than 5 minutes. For instructions on replacing these components, see the HP ProLiant DL380 G6 Server Maintenance and Service Guide on the HP website at http://www.hp.com/support/manuals. Under Servers, click ProLiant ml/dl and tc series servers, and select your product.
8Power supplies specifications and cable information