Configuration scenarios
Example configurations
The following configuration examples were calculated using the HP Blade Power Sizer Tool. This tool is designed for facilities planning purposes only. Values obtained from the tool are based on worst case loads. Whenever possible, actual measurements are recommended. Measurements should be made with the intended configuration, application loading, and ambient environment.
Actual power usage will vary depending on application loading, ambient temperature, and other factors.
Example minimum configuration
This power summary is based on the following configuration:
•HP BladeSystem c7000 enclosure (1)
•Ethernet
•HP ProLiant BL460c Server Blades (2)
o
o 36GB
Total system leakage current per branch | 0 mA |
|
|
Total system inrush current per branch (2 mS) | 70 A |
|
|
Total system weight (includes power and rack) | 197 kg (435 lb) |
|
|
Power credentials | Idle |
| 100% utilization | Circuit sizing | ||
|
|
|
|
|
|
|
Total input power | 601 | W | 764 | W | 1109 | W |
|
|
|
|
|
|
|
Total input VA | 613 | VA | 779 | VA | 1132 | VA |
|
|
|
|
| ||
BTU | 2049 BTU | 2604 BTU | 3781 | BTU | ||
|
|
|
| |||
Total input current | 2.95 A | 3.75 A | 5.44 A | |||
|
|
|
|
|
|
|
Total airflow (CFM) | 116 |
| 131 |
| 156 |
|
|
|
|
|
| ||
Total airflow (CMM) | 3.280 | 3.713 | 4.429 |
| ||
|
|
|
|
|
|
|
Example typical configuration
This power summary is based on the following configuration:
•HP BladeSystem c7000 enclosure (1)
•HP Virtual Connect Ethernet Modules (2)
•HP Virtual Connect Fibre Channel Modules (2)
Configuration scenarios 54