Transfer Switch
Auxiliary Contacts
Auxiliary contacts TSNa3,
Manual Disconnect Switch
The MDS (Manual Disconnect Switch) is mounted on the TRC board. This switch isolates the power source to the switching mechanism. Then the automatic transfer switch can only be operated manually with the handle.
CAUTION: Disconnect normal and emergency power sources before using handle to transfer the contacts.
TEST push button
The TEST push button simulates a loss of power from the normal source and causes the Control Module to initiate transfer to the emergency source.
Optional Features
The items described in this section are a few of the optional features available with the
BYPASS/RETRANSFER TO NORMAL push button (S1)
This option is standard for combination Fire Pump Controller with automatic transfer switch to meet NFPA 20 specifications.
Pressing this button allows the transfer switch to retransfer to the normal position bypassing the RETRANSFER TO NORMAL SOURCE time delay.
Phase Rotation Monitor (H1)
The PRM (Phase Rotation Monitor) contacts open if the phase rotation of the normal power source is not correct. If the proper phase sequence is not sensed, the
Auxiliary Contacts (A1–A4)
One additional NO/NC set of contacts may be added to the normal and the emergency source side of the transfer switch. The contacts are rated for pilot duty: 10 A at 125 or 250 VAC.
BYPASS/TRANSFER TO EMERGENCY push button (S2)
This push button overrides the time delay to transfer to the emergency source.
Page 8 of 16 Pages