IMS Driver Supply Cable AWG Table
1 Ampere (Peak)
2 Amperes (Peak)
3 Amperes (Peak)
4 Amperes (Peak)
Length (Feet)
Minimum AWG
Length (Feet)
Minimum AWG
Length (Feet)
Minimum AWG
Length (Feet)
Minimum AWG
10 25 50* 75* 100*
10 25 50* 75* 100*
10 25 50* 75* 100*
10 25 50* 75* 100*
20 20 18 18 16
20 18 16 14 14
18 16 14 12 12
18 16 14 12 12
* Use the alternative methods innustrated in
Examples B and C when the cable length is
≥
50
feet. Also, use the same current rating when the
alternate AC power is used.
Driver Supply Cable Wire SizeNOTE: These recommendations will provide optimal
protection against EMI and RFI. The actual cable type,
wire gauge, shield type and filtering devices used are dependent
on the customer’s application and system.
NOTE: Always use Shielded/Twisted Pairs for the IMS Driver
DC Supply Cable, the AC Supply Cable and the IMS Driver to
Motor Cable.