REPLACING ORIFICE:
This can be accomplished without removing the unit from its mounting or plumbing.
1.Turn off supply pressure and unscrew the brass orifice assembly located on the side of the housing with the gauge port.
NOTE: Small sealing
2.Install the new orifice assembly making sure the
CLEANING INTERNAL SUPPLY VALVE:
1.Turn off the supply pressure.
2.Use a 9/16" socket or wrench to unscrew the brass plug in the bottom of the transducer. NOTE: Take care not to lose the supply valve spring which is retained by the bottom plug.
3.Clean out any dirt or debris and reassemble, making sure the stem of the supply valve is nested in the supply valve spring.
AGENCY APPROVALS, SPECIAL NOTES, AND CAUTIONS
INTRINSIC SAFETY
All 510 and 511 Series transducers are rated intrinsically safe by both FM and CSA for:
CLASS I, DIVISION 1, GROUPS A,B,C,D HAZARDOUS LOCATIONS.
Proper
ENTITY PARAMETERS:
Vmax = 28 V, Imax = 150 mA, Ci = 0.22uF, Li = 0 mH.
Voc and Isc of a barrier shall not exceed Vmax and Imax of the transducer. (Li + Lwiring) and (Ci + Cwiring) shall not exceed La and Ca of a barrier.
NOTICE: For proper FM and CSA approved
NONINCENDIVE
All 510 and 511 Series transducers are approved as NONINCENDIVE by FM and approved as suitable by CSA for:
CLASS I, DIVISION 2, GROUP A, B, C, D HAZARDOUS LOCATIONS.
A barrier is not necessary when these transducers are in these locations.
ENCLOSURES
Compliance with NEMA 4X and CSA ENC4 enclosure ratings require that the
7