Tumblers – 120 and 170
4-08-45
13
Figure 2
NOTE: Do not install wire mesh or screen in
exhaust duct opening to avoid lint build-up or
impacting proper discharge of air from tumblers.
NOTE: Where exhaust duct pierces a combustible
wall or ceiling, the opening must be sized per local
codes.
NOTE: Inside of duct must be smooth. Do not use
sheet metal screws to join sections.
Consult your local building code for regulations which
may also apply.
TMB2103N
1Removable strip of panel in framing wall to permit removal of tumbler from framing wall
2Partition or bulkhead
3Minimum distance between exhaust opening and roof, ground or other obstruction: 36 in. (914 mm)
42 in. (51 mm) minimum clearance on both sides of duct
5Exhaust airflow – maximum length of duct: 14 ft. (4.3 m)
TMB2103N