Johnson Controls AC6B Led Diagnostic Indicators, Operational Mode Detection, Status Code Display

Models: AL6B SERIES AC6B 16 SEER - CZF

1 18
Download 18 pages 44.69 Kb
Page 13
Image 13
LED DIAGNOSTIC INDICATORS

 

 

562156-UIM-A-0610

TABLE 2: TEST Input Functionality

 

 

 

 

Duration of

Control Behavior with no system

Control behavior with system

connection (seconds)

master signals present

master signals present

 

 

 

< 2

No response

No response

 

Display compressor type TS, Ultratech, or

Bypass ASCD (Reduce timer to zero immediately).

 

If Y1 (thermostat or communication) is present and the

 

single stage compressor, Ignore LPS

 

high-pressure switch is closed, contactors will be energized.

 

 

 

 

 

 

Clear soft lockout

Clear soft lockout

2 <

 

 

Clear hard lockout

Clear hard lockout

 

 

 

 

Reset TS anticipation mode counter

Reset TS anticipation mode counter

 

to zero for TS systems.

to zero for TS systems.

 

 

 

 

 

Reduce TS staging delays for TS

 

 

systems as described below.

 

 

 

Connection removed

Resume normal LED display

 

Connection not removed

Nothing more than previously explained

 

LED DIAGNOSTIC INDICATORS

The control includes two LED’s that display diagnostic information. LED1 is red and LED2 is green. These LED’s are used to display oper- ational mode, fault information. A third LED, LED3 is used to display status information. LED3 is yellow. These LED’s are used to display operational mode, status, and fault information.

OPERATIONAL MODE DETECTION

The control can be used in a variety of applications including AC units with multistage compressors. The control uses various inputs to deter- mine the proper mode of operation.

The control senses the connections that are made to M, M1, and M2 terminals and determines the correct operational mode for the control. This is done each time power to the control is cycled. Therefore, it is important that no loads be attached to the M1 or M2 terminals of the control for single-stage compressors, and no loads be attached to the M1 terminal of the control for a scroll two-stage compressor.

Do not connect any loads to the M1 or M2 terminals of the control for single-stage compressors, and no loads should be attached to the M1 terminal of the control for scroll two-stage compressor. Incorrect system behavior could result.

OPERATIONAL MODE DISPLAY

The control will display its active operational mode using the onboard LED’s when the TEST pins are connected while no thermostat signals are energized. Table 3 "Operational Mode Display" describes the oper- ational modes. The control will display the operational mode as long as the TEST pins are shorted and no thermostat signals are energized. When the TEST pin short is removed, the control will return to normal LED displays.

TABLE 3: Operational Mode Display

Compressor Type

LED1 (Red)

LED2 (Green)

 

 

 

Single Stage Compressor

1 flash

---

 

 

 

TS Compressor

2 flashes

---

 

 

 

UltraTech Compressor

3 flashes

---

 

 

 

STATUS CODE DISPLAY

The control also provides status codes using the LED’s. Status codes indicate the state of the operation of the unit but do not represent a fault. Tables 4 & 5 describes the LED displays during status codes. Sta- tus codes will not be displayed when a fault code is present.

TABLE 4: Status Code Display

Description

Required Condition

LED1 (Red)

 

LED2 (Green)

 

 

 

 

 

 

No power to control

No power to control

OFF

 

OFF

 

TS – M & M1 energized,

 

 

 

First-stage compressor operation – TS or UltraTech

UltraTech – M energized,

OFF

 

ON

 

Single Stage - NA

 

 

 

 

 

 

 

 

 

Second-stage compressor operation - TS, UltraTech, or

TS and UltraTech – M & M2 energized,

ON

 

ON

Single Stage

Single Stage – M energized

 

 

 

 

 

 

 

 

 

 

Control normal operation – no communication or call for

No faults active, Y1 or Y2 not present

OFF

 

2s ON / 2s OFF

compressor present

 

 

 

 

 

 

 

 

 

 

 

 

Control normal operation – in ASCD period

No faults active, Y1 or Y2 present,

OFF

 

0.1 sec ON /

ASCD timer not expired

 

0.1 sec OFF

 

 

 

 

 

 

 

 

 

TABLE 5: Status Code Display

 

 

 

 

 

 

 

 

 

 

 

Description

 

Required Condition

 

 

LED3 (Yellow)

 

 

 

 

 

 

Control normal operation – with active communication present

System is active and presently communicating successfully.

0.1 sec ON /

0.1 sec OFF

 

 

 

 

 

 

 

 

 

Control powered – without active communication present

 

System has 24 VAC present and the microprocessor is active.

2s ON / 2s OFF

Johnson Controls Unitary Products

13

Page 13
Image 13